AMC2 Extension
6

Technical Data

Power supply
10 to 30 Vdc
or via the AMC2-4W
Power consumption
AMC: 5 VA
Peripheral devices: using the PSU-60
Connectors
Pluggable screw connectors
Protection class
IP30
Environment temperature
13° C to 35° C (55° F to 95° F)
Humidity
Up to 95%, without condensation
Housing material
ABS with OC (UL 94 V-0)
Dimensions
(W/H/D) 232 x 90 x 63mm (8.9 x 3.5 x 2.5 in)
Weight
approx. 0.53kg (1.2lb)
Bosch Access Systems GmbH
Four Wiegand interfaces for up to four card readers
(Output rating: 280 mA)
Eight relay outputs
maximum ratings (wet and dry):
switching voltage: 30 Vdc
switching current: 1,25 A
operating ratings (wet and dry):
1,25 A @ 30 Vdc
2 A @ 12 Vdc
1,5 A @ 24 Vdc
Eight analog inputs with tamper detection; only connect dry contacts
RS-485 extension interface:
Transfer rate: 9,6 kBit/s,
no parity, 8 bit, 2 stop bit
Tamper contact for external enclosures
up to 55 VA
constant load: 25 VA
Installation Manual