Installation Instructions
Remote I/O Adapter Module
(Catalog Number 1747-ASB)
Inside ................................................................................................page
Hazardous Location Considerations .........................................................2
Environnements dangereux ......................................................................2
1747-ASB Module Overview ....................................................................3
Required Tools and Equipment .................................................................4
Determining System Power Requirements...............................................4
Slot Addressing.........................................................................................5
Configuring the Module ............................................................................6
Installing the Module..............................................................................10
Connecting RIO Link Devices ..................................................................11
Wiring a Processor Restart Lockout Switch ...........................................14
Installing I/O Module Addressing Labels ...............................................15
Performing System Start-up ...................................................................17
Checking Operation.................................................................................17
Specifications .........................................................................................18
For More Information ..............................................................................19

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1747-ASB and is the answer not in the manual?

Questions and answers

Summary of Contents for Allen-Bradley 1747-ASB

  • Page 1: Table Of Contents

    Installation Instructions Remote I/O Adapter Module (Catalog Number 1747-ASB) Inside ....................page Hazardous Location Considerations ............2 Environnements dangereux ..............2 1747-ASB Module Overview ..............3 Required Tools and Equipment ..............4 Determining System Power Requirements..........4 Slot Addressing..................5 Configuring the Module ................6 Installing the Module................10 Connecting RIO Link Devices ..............11...
  • Page 2: Hazardous Location Considerations

    Remote I/O Adapter Module Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations. EXPLOSION HAZARD WARNING •...
  • Page 3: 1747-Asb Module Overview

    (slot 0) of a 1746 remote chassis, where the SLC processor normally resides. The 1747-ASB module is an adapter, or slave, on the RIO link, and the master of the remote chassis and remote expansion chassis in which it is installed. Remote expansion chassis are optional.
  • Page 4: Required Tools And Equipment

    Review the power requirements of your system to ensure that the chassis supports placement of the 1747-ASB module. The adapter consumes 600 mA at 5V dc. For a detailed list of device load currents, refer to the SLC 500 Fixed Hardware Style Installation and Operation Manual, publication number 1747-6.21;...
  • Page 5: Slot Addressing

    Slot Numbering The 1747-ASB module is capable of controlling 30 slots. When expansion chassis are used, the 1747-ASB module treats all of the I/O modules as if they are installed in a single chassis. The remote chassis and remote expansion chassis slots are numbered from 0 to 30.
  • Page 6: Configuring The Module

    Slot For more information on addressing, refer to the Remote I/O Adapter Module User Manual, publication number 1747-6.13. Configuring the Module The 1747-ASB module parameters are configured by three DIP switches, shown below. DIP Switches Publication 1747-IN014C-EN-P - January 2003...
  • Page 7 • Starting Logical Group Number (Logical Group) - is the 1747-ASB module’s starting logical group number within the scanner’s image. • Baud Rate (Baud Rate) - is the 1747-ASB module’s RIO link communication rate. The baud rate must be the same for all adapters on the RIO link.
  • Page 8 Remote I/O Adapter Module Dip Switch Settings Local Rack Number Logical Rack Number Bit 5 ON = 0 OFF = 1 (Most Significant Bit) Logical Rack Number Bit 4 Logical Rack Number Bit 3 Local Group Number Logical Rack Number Bit 2 Group Logical Rack Number Bit 1 Logical Rack Number Bit 0 (LSB)
  • Page 9 ASB Module Image Size Bit 1 Primary/Complementary Chassis ASB Module Image Size Bit 0 Primary Complementary 1747-ASB Module Image Size Groups If you are not using complementary I/O, you must set SW2-3 to IMPORTANT the OFF, or complementary, position. Publication 1747-IN014C-EN-P - January 2003...
  • Page 10: Installing The Module

    Remote I/O Adapter Module Hold Last State Hold Last State Hold Last State Processor Restart Lockout Do not Hold Last State (default) Link Response Last Chassis/PLC-3 Backup Addressing Mode Bit 1 (MSB) Processor Restart Lockout (after lost communications) Addressing Mode Bit 0 (LSB) Specialty I/O Mode Automatic Restart (default) I/O Module Keying...
  • Page 11: Connecting Rio Link Devices

    2. Install the module in slot 0 of the remote chassis by aligning the circuit board with the chassis card guide. The 1747-ASB module must be installed only in slot 0 (the left slot) of the remote chassis. Do not install the 1747-ASB module in the remote expansion chassis.
  • Page 12 No two devices can be connected to the same point on the link. IMPORTANT An example of correct and incorrect link wiring is shown below. Correct Link Wiring 1747-ASB Module To Scanner 1747-ASB Module 1747-ASB Module Incorrect Link Wiring...
  • Page 13 If the signal integrity on the RIO link is compromised by IMPORTANT environmental noise, improper termination, and/or improper cable installation, the 1747-ASB module scan rate drops. This is indicated by a pronounced flickering of the status display. To Scanner’s Connector...
  • Page 14: Wiring A Processor Restart Lockout Switch

    Wiring a Processor Restart Lockout Switch When processor restart lockout is enabled (SW3-2) and communications are restored, the 1747-ASB module does not respond to any type of communication, or communication commands until terminals IN and RET are momentarily shorted together. This occurs while the RIO scanner is attempting to communicate with the 1747-ASB module.
  • Page 15: Installing I/O Module Addressing Labels

    Remote I/O Adapter Module Installing I/O Module Addressing Labels Attach the Remote PLC or Remote SLC label to the outside bottom of each I/O module in your 1747-ASB chassis, as shown below. Fill out each label completely. INPUT INPUT 0 - 7...
  • Page 16 The octal filter and door label kits must be used when working with a PLC processor as a master. Adhere the octal labels over the existing decimal labels, as shown below. Contact your local Allen-Bradley distributor if you need to order additional label kits.
  • Page 17: Performing System Start-Up

    Follow the steps below: 1. Cycle power one last time in save mode (SW3-8 ON). 2. Remove power from the system. 3. Remove the 1747-ASB module and set SW3-8 to the OFF position (check mode). 4. Replace the 1747-ASB module in slot 0.
  • Page 18: Specifications

    Remote I/O Adapter Module Specifications Adapter Operating Specifications Backplane Current Consumption 375 mA at 5V dc Operating Temperature 32°F to 140°F (0°C to 60°C) Storage Temperature -40°F to +185°F (-40°C to +85°C) Humidity 5% to 95% non-condensing Noise Immunity NEMA standard ICS 2-230 Vibration Displacement: 0.015 inch, peak-to-peak at 5-57 Hz Acceleration: 2.5Gs at 57-2000 Hz...
  • Page 19: For More Information

    Remote I/O Adapter Module For More Information Refer to this Document Pub. No. A more detailed description on how to install and use Remote I/O Adapter Module 1747-6.13 your Remote I/O Adapter Module. User Manual A more detailed description on how to install and use Remote I/O Scanner Module 1747-6.6 your Remote I/O Scanner Module (1747-SN).
  • Page 20: Publication 1747-In014C-En-P - January

    Please contact your local Rockwell Automation representative for return States procedure. Rockwell Automation, Allen-Bradley, SLC 500, PLC, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1747-IN014C-EN-P - January 2003...

Table of Contents