ArmorBlock LP 16 Input Module
Cat. No. 1792-IB16LP
This 1792 ArmorBlock I/O block module (Cat. No. 1792-IB16LP
contains I/O circuits, a built-in power supply, and a built-in DeviceNet
I/O adapter. Because of its sealed housing, this 1792 I/O block requires
no enclosure. It is compatible with PLC or SLC programmable
controllers using DeviceNet scanners. The I/O values are accessible
from the PLC or SLC programmable controller data table.
This ArmorBlock-LP module has no switches to set. You set module
parameters using the DeviceNet Manager Software (cat. no. 1787-MGR)
or similar configuration tool.
Contents
This box contains:
1 ArmorBlock–LP module
Package containing 10 write-on indicator tabs, and 7 micro caps
1 DeviceNet right hand aluminum T-port tap (part number 97042401)
Installation Instructions
European Union Directive Compliance
If this product is installed within the European Union or EEA regions
and has the CE mark, the following regulations apply.
EMC Directive
This apparatus is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC).
The product described in this manual is intended for use in an industrial
environment.
ArmorBlock is a trademark of Allen-Bradley Co. Inc.
Installation Instructions
Publication 1792-5.6 – September 1997
)

Advertisement

loading
Need help?

Need help?

Do you have a question about the ArmorBlock-LP 1792-IB16LP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Allen-Bradley ArmorBlock-LP 1792-IB16LP

  • Page 1 EMC Directive This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC). The product described in this manual is intended for use in an industrial environment. ArmorBlock is a trademark of Allen-Bradley Co. Inc. Publication 1792-5.6 – September 1997...
  • Page 2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information that the above norm requires, see the appropriate sections in this manual, as well as the following Allen-Bradley publications: Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1...
  • Page 3: Mounting Dimensions

    ArmorBlock-LP 16 Input Module Set up a system (as shown below) to communicate with your ArmorBlock module to set the node address and communication rate to meet your system requirements. Power from 9V dc power supply adapter 1770-KFD RS-232 module Host computer with DeviceNetManager software...
  • Page 4 ArmorBlock-LP 16 Input Module Connect the Wiring to the ArmorBlock Module This module uses quick disconnect, screw-on style connectors for: I/O input wiring the DeviceNet connector 5-pin DeviceNet Mini-connector Eight 5-pin Input Micro-connectors 30197–M Seven micro plugs are included with your module. Use these plugs to cover and seal unused ports.
  • Page 5 ArmorBlock-LP 16 Input Module Connecting the DeviceNet Wiring Connect DeviceNet wiring to the 5-pin mini-connector on the end of the block. Connections are shown below. DeviceNet Mini-Connector Pin 1 = Drain (Bare) Pin 2 = V+ (Red) Note: Colors are DeviceNet standard Pin 3 = V–...
  • Page 6 ArmorBlock-LP 16 Input Module Refer to the table below for the word/bit definitions. Produces 1 Produces 2 Produces 3 Reserved Where: I = Input IS = Sensor source voltage fault Word Description Produces 00–07 Input bits – bit 00 corresponds to input 1A, bit 01 to input 2A, and so on. 0 = input off;...
  • Page 7 ArmorBlock-LP 16 Input Module Troubleshoot with the Indicators The ArmorBlock I/O module has the following indicators: Network status indicator (NS) Module status indicator (MS) Individual I/O status indicators (A, B) Power Status indicators – module power – sensor power – sensor short circuit OVL = Sensor Short NS = Network Status Indicator...
  • Page 8 ArmorBlock-LP 16 Input Module Network Status Indicator NS Indication Status Flashing Green On-line, not connected Solid Green Link OK, on-line connected Flashing Red At least 1 I/O connection is in the timed-out state Solid Red Incorrect baud rate, or a duplicate Mac ID exists Module Status Indicator MS Indication Status...
  • Page 9: Specifications

    ArmorBlock-LP 16 Input Module Specifications 16 Input Module – Cat. No. 1792-IB16LP Input Specifications Inputs per Block 16 sinking On-state Voltage Range 12–30V dc On-state Current Maximum 15.0mA @ 30V dc Minimum 1.6mA @ 12V dc Off-state Voltage Maximum 5V dc Off-state Current Minimum 0.8mA...
  • Page 10 Africa, Republic Spain Sweden Switzerland Taiwan Thailand Turkey United Arab Emirates United Kingdom United States Uruguay Venezuela Yugoslavia Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444 Publication 1792-5.6 – September 1997 PN955128–53...