10 ControlLogix AC (10-265V) DC (5-150V) Isolated Relay Module

Wire the Removable Terminal Block

Wire the RTB with a 1/8 inch (3.2mm) maximum flat-bladed
screwdriver before installing it onto the module.
When you connect or disconnect the Removable
WARNING
Terminal Block (RTB) while field side power is on, an
electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Spring Clamp RTB
1. Strip 7/16 inch (11mm) maximum
length of wire.
2. Insert the screwdriver into the
inner hole of the RTB.
3. Insert the wire into the
open terminal and
remove the screwdriver.
Publication
1756-IN513D-EN-P - November 2003
1. Strip 3/8 inch (9.5mm) maximum
length of wire.
2. Insert the wire into the open terminal.
3. Turn the screw clockwise to close the
terminal on the wire.
20860-M
Cage Clamp RTB
20859-M