4.12.1 Parameters Service Level - Siemens RDG400 Basic Documentation

Room thermostat with display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Name
Service level
P01
Control sequence
P02
User operating mode profile (mode button)
P04
Selection of °C or °F
P05
Sensor calibration (intern, extern)
P06
Standard temperature display
P07
Display info line
(2nd line of LCD)
P08
Comfort setpoint
P09
Minimum setpoint in Comfort mode
P10
Maximum setpoint in Comfort mode
P11
Energy Saving heating setpoint
P12
Energy Saving cooling setpoint
P14
Button lock function
Note
Siemens
Building Technologies

4.12.1 Parameters Service level

Factory setting
When 2-pipe /
2-stage:
1 = Cooling only
When 4-pipe:
4 = H and C
1
0 (°C)
0 K
0
0
21 °C
5 °C
35 °C
15 °C
30 °C
0
Parameter display depends on selected application and function
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation
Functions
Range
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E Saving - Prot
0 = Degrees Celsius (°C)
1 = Degrees Fahrenheit (°F)
– 3 ... 3 K
0 = Room Temperature
1 = Setpoint
0 = --- (No display)
1 = °C and °F
5 ... 40 °C
5 ... 40 °C
5 ... 40 °C
OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max)
OFF, WHeatE-saving ... 40 °C;
(WHeatE-saving = 5 °C min)
0 = Unlocked
1 = Auto locked
2 = Manual locked
0..1
29 / 42
CE1P3182en
28 May 2009