4.12.2 Parameters Expert Level, Diagnostics & Test - Siemens RDG400 Basic Documentation

Room thermostat with display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Name
Expert level
P30
P-band / Switching differential in heating mode
P31
P-band / Switching differential in cooling mode
P32
P-band / Switching differential for radiator
P33
Dead zone in Comfort mode
P34
Setpoint differential (w
P35
Integral time
P36
Heating / cooling changeover switching point
cooling (X1/X2)
P37
Heating / cooling changeover switching point
heating (X1/X2)
P38
Functionality of X1
P39
Operating action of X1 if digital input
P40
Functionality of X2
P41
Operating action of X2 if digital input
P42
Functionality of D1
P43
Operating action of D1 if digital input
P44
Running time of Y1/Y2 output
(only when modulating PI control)
P46
Output Y1/Y2 (if not parameterized as 3-pos.)
P51
Floor heating limit temperature
P63
Minimum output limitation air flow signal
P64
Maximum output limitation air flow signal
P65
Protection heating setpoint
P66
Protection cooling setpoint
P68
Prolong Comfort period
P69
Temporary setpoint Comfort
(see also Comfort setpoint P08)
P71
Reload factory settings
Note
30 / 42
Siemens
Building Technologies
4.12.2 Parameters Expert level, diagnostics & test
Factory setting
2 K
1 K
2 K
2 K
)
2 K
D
5 min
16 °C
28 °C
1: = Ext. sensor
0 (N.O.)
2 = H/C changeover 0 = --- (no function)
0 (N.O.)
3 = Op. mode
changeover
0 (N.O.)
150 s
ON/OFF (1)
OFF
0%
100%
8 °C
OFF
OFF
OFF
OFF
P46: Setting to 2-position or 3-position is done with DIP 4
RDG100.../RDG110.../RDG140.../RDG160... Basic Documentation
Functions
Range
0.5 ... 6 K
0.5 ... 6 K
0.5 ... 6 K
0.5 ... 5 K
0.5 ... 5 K
0...10 min
10...25 °C
27...40 °C
0 = --- (no function)
1 = Room temp ext / Return temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0 = Normally open
/ Open
1 = Normally closed / Closed
1 = Room temp ext / Return temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0 = Normally open
/ Open
1 = Normally closed / Closed
0 = --- (no function)
2 = H/C changeover (DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0 = Normally open / Open
1 = Normally closed / Closed
20...300 sec
1 = 2-position
2 = PWM
OFF, 10..50 °C
0...P64 (%)
P63...100 (%)
OFF, 5 ... W Cool Prot;
(W Cool Prot = 40 °C max)
OFF, W Heat Prot ... 40;
(W Heat Prot = 5 °C min.)
OFF; 15 ... 360 min
OFF = Disabled
ON = Enable
OFF = Disabled
ON = Reload start
0..6
0..6
0..6
CE1P3182en
28 May 2009