Name
Service level
P01
Control sequence
P02
Operating mode profile (operating mode
button)
P04
Selection of °C or °F
P05
Sensor calibration (internally, externally)
P06
Standard temperature display
P07
Display info line
(2nd line of LCD)
P08
Comfort setpoint
P09
Min. setpoint for Comfort mode
P10
Max. setpoint for Comfort mode
P11
Economy heating setpoint
P12
Economy cooling setpoint
P14
Button lock function
ü
Parameter available
Note:
30/44
Siemens
Building Technologies

4.12.1 Parameters of the "Service level"

Factory setting
1 = cooling only
1
0 (°C)
0 K (0 °F)
0
0
21 °C (70 °F)
5 °C (41 °F)
35 °C (95 °F)
15 °C (59 °F)
30 °C (86 °F)
0
· Parameter display depends on selected application and function
· P01 is available for "Single-duct" and "Single duct & heating/cooling coil" only
RDG400 Basic Documentation
Range
0 = heating only
1 = cooling only
2 = H/C changeover manually
3 = H/C changeover automatically
1 = Comfort – Protection
2 = Comfort - Economy - Protection
0 = degrees Celsius (°C)
1 = degrees Fahrenheit (°F)
– 3...3 K (– 6...6 °F)
0 = room temperature
1 = setpoint
0 = --- (no display)
1 = °C and °F
5...40 °C (41...104 °F)
5...40 °C (41...104 °F)
5...40 °C (41...104 °F)
OFF, 5 °C (41 °F) ...WcoolE-saving;
(WcoolE-saving = 40 °C (104 °F) max.)
OFF, WHeatEco...40 °C (104 °F);
(WHeatEco = 5 °C (41 °F) min.)
0 = unlocked
1 = auto locked
2 = manual locked
ü
ü
ü
ü
ü
0..1
ü
ü
ü
ü
ü
ü
CE1P3182en
2015-05-20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents