Operation - Siemens RDG400 Basic Documentation

Room thermostat with display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Layout
Button operation
User action
Press left button
Press left button >3 sec
Remain on left button and
turn rotary knob clockwise
Remain on left button and
turn rotary knob anti-clockwise
Press left button while "Operating mode
switch-over" is activated
Press right button >3 sec
Press right button
Rotate rotary knob
Press left + right button >3sec, release,
then press right button >3sec
Press left button + right button 3sec,
release, press left button 3sec,
then rotate rotary knob counter-clockwise
min ½ rotation
Siemens
Building Technologies
5.2

Operation

See also the operating instructions B3181 enclosed with the thermostat.
1
1 Operating mode button / Esc
2 Protection mode and OK
3 Rotary knob for setpoint and parameter adjustment
• When the thermostat is in normal operation, the actual operating mode and
status is indicated by symbols.
• When a button is pressed, the RDG goes into the Mode selection
The LCD backlight will turn on, all possible mode selection options (symbols) will
turn on, indicator element (arrow) will appear on the current mode/status.
• When the button is pressed again, the indicator element will toggle to the next
mode symbol and so on.
• After the last press and a timeout of 3 sec, the new selected mode is confirmed,
the other elements disappear.
• After a timeout of 20 sec the LCD backlight will turn off
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation
Handling
2
3
Effect, description
Go into Operating mode selection
Set thermostat to Protection mode
Activate temporary timer "Extend presence"
and set the time (details see page 16)
Activate temporary timer " Extend absence"
and set the time (details see page 16)
Activate " Extend Comfort mode"
(details see page 16)
Activate/deactivate button lock
Change to protection mode and back
Adjust the room temperature setpoint
Go into parameter mode Service level
Go into parameter mode Expert level,
diagnostics & test
33 / 42
CE1P3182en
28 May 2009

Hide quick links: