Operation
Error
three-
Event
code
level
1
no
Remaining control
deviation
no
Device not in
2
automatic mode
no
Binary input BE1
3
or BE2 active
yes
Limit
4
Stroke number
exceeded
yes
Direction change
5
limit exceeded
yes
Lower limit stop
6
limit exceeded
7
yes
Limit
of upper limit stop
exceeded
no
Limit
8
Dead zone
adaptation
exceeded
yes
Partial stroke test
9
exceeds reference
step time
10
yes
General control
valve malfunction
11
yes
Pneumatic leakage C. LEAK¸OFF
132
Parameter-
Error message
setting
disappears if...
always active
... the control
deviation has
disappeared again.
47. FCT= nA
... the device is
or =
nAB
switched to automatic
mode.
47. FCT= nAB
... the binary input is
and binary function
no longer activated.
BIN1 or BIN2 at "on"
... the stroke counter
L. STRK¸OFF
is reset or the
thresholds are
increased
... the direction
O. DCHG¸OFF
change counter is
reset or the
thresholds are
increased
... the deviation of the
F. ZERO¸OFF
stop disappears or
39.YCLS = do or up
the device was
do
re-initialized.
... the deviation of the
G. OPEN¸OFF
stop disappears or
39.YCLS = up or up
the device was
do
re-initialized.
... the value has
E. DEBA¸OFF
fallen below the limit
34.DEBA = Auto
again.
... a partial stroke test
A. PST¸OFF
is performed
successfully within
the reference step
time or the function is
deactivated.
... the position is back
b. DEVI¸OFF
within a narrow
corridor between
guide value and
model, or the function
is deactivated.
... the leakage falls
below the set
thresholds, or the
function is
deactivated.
Possible
causes
Compressed air
missing, actuator
fault, valve fault
(e.g. blockage).
The device is
configured or is in
manual mode.
The contact
connected to the
binary input became
active (e.g. stuffing
box monitoring,
overpressure,
temperature switch).
The sum of the
distance covered by
the actuator exceeds
one of the set
thresholds.
The number of
changes of direction
exceeds one of the
set thresholds.
Wear of the valve
seat, deposit or
foreign matter in
the valve seat,
mechanical
misadjustment, friction
clutch misadjusted.
Wear of the valve
seat, deposit or
foreign matter in
the valve seat,
mechanical
misadjustment, friction
clutch misadjusted.
Increased stuffing box
friction, mechanical
batches of the
position feedback.
Valve jams or is
rusted in place,
increased friction
actuator fault, valve
fault, valve jams,
increased friction,
compressed air drop
Pneumatic leakage
SIPART PS2 Manual