Siemens SIPART PS2 6DR50xx Manual page 128

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

Operation
19 PAVG
20 P0
21 P100
22 IMPUP
23 IMPDN
24 DBUP
25 DBDN
128
Average position value
The comparison average calculated last is displayed here. There are
also the following status messages:
OFF
S
The basic function is deactivated in the configuration menu.
IdLE (inactive)
S
The function has not been started yet.
rEF (reference average is calculated)
S
The function was started and the reference interval is currently
active.
COMP (comparison average is calculated)
S
The function was started and the comparative interval is currently
active.
Potentiometer value lower stop
and
Potentiometer value upper stop
These two values indicate the measured values of the position
displacement sensor (potentiometer) at the lower or upper limit stop,
as determined during the automatic initialization. With manual initializa-
tion, the values of the manually approached end positions can be found
here.
Pulse length up
and
Pulse length down
During the initialization phase, the smallest pulse lengths are deter-
mined, with which a movement of the actuator can be achieved.
They are determined separately for the "Up" direction and the "Down"
direction and displayed here.
These two parameters can be set for special applications (see chap-
ter 4.7, page 143).
Dead zone up
and
Dead zone down
The dead zone of the controller in "Up" direction or in "Down" direction
is displayed here. The values correspond either to the manually set
value of parameter "34.DEBA" or to the value automatically adapted by
the device if "DEBA" was set to "Auto".
SIPART PS2 Manual
A5E00074631--06

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents