Pneumatic Connection - Siemens SIPART PS2 6DR50xx Manual

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

3.5

Pneumatic Connection

!
.
.
SIPART PS2 Manual
A5E00074631--06
WARNING
For reasons of safety, the pneumatic power may only be supplied after
assembly when the positioner is switched to operating level P manual
operation with electrical signal applied (as-delivered state, see
figure 4-4, page 92).
NOTE
Note the air quality! Oil-free industrial air, solid content < 30 μm, pressure
dew point 20 K below the lowest ambient temperature (chapter 7 "Techni-
cal Data", page 153).
Connect a manometer block for supply air and actuating pressure if
S
necessary.
Connection by female thread G 1/4 DIN 45141 or 1/4" NPT:
S
P
Supply air 1.4 to 7 bar
Z
Y1
Actuating pressure 1 for single- and double-acting actuators
Y2
Actuating pressure 2 for double-acting actuators
E
Exhaust air outlet (remove silencer if necessary)
see figure 2-4 and 2-5, page 19.
Safety position when the electric power supply fails:
S
single-acting:
Y1
double-acting:
Y1
Y2
Connect actuating pressure Y1 or Y2 (only in double-acting actua-
S
tors) according to the desired safety position.
Connect supply air to P
S
NOTE
In order for spring-loaded pneumatic actuators to be able to reliably
exploit the maximum possible travel, the supply pressure must be
sufficiently greater than the maximum required final pressure of the
actuator.
After installing the device, check the pneumatic connections of the entire
assembly for leakage. Any leakage would cause not only continuous
consumption of compressed air but also would cause the positioner to
continually endeavor to compensate for the variance in position, leading
in time to premature wear of the whole control mechanism.
Preparing for Operation
deaerated
Max. Actuating pressure
(supply air pressure)
deaerated
.
Z
71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents