Siemens SIPART PS2 6DR50xx Manual page 115

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

E. DEBA
E1.LEVL3
F. ZERO
F1.LEVL1
F2.LEVL2
F3.LEVL3
SIPART PS2 Manual
A5E00074631--06
Dead zone monitoring
This parameter activates the monitoring of the dead zone adaptation.
Prerequisite for the function is the setting of parameter "34.DEBA"
= Auto.
Threshold for the monitoring of the dead zone adaptation.
This value (%) can be used for the automatic adaptation of the dead
zone. If the dead zone exceeds the set value, the threshold 3 error
message is triggered. The three-level error message is not imple-
mented for dead zone monitoring.
Zero point offset
This function is for detecting when the lower stop has changed its value
compared to the value during initialization by more than the set
thresholds. Monitoring is only possible if the valve is within the tight
closing function. The activation of the "bottom tight closing function"
(parameter "39.YCLS") is therefore prerequisite.
Threshold 1
First threshold for monitoring the lower limit stop. If the set absolute
value is exceeded during "bottom tight closing", this will trigger the
threshold 1 error message.
Threshold 2
Second threshold for monitoring the lower limit stop. If the set absolute
value is exceeded during "bottom tight closing", this will trigger the
threshold 2 error message.
Threshold 3
Third threshold for monitoring the lower limit stop. If the set absolute
value is exceeded during "bottom tight closing", this will trigger the
threshold 3 error message.
Operation
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents