51.XDIAG
.
SIPART PS2 Manual
A5E00074631--06
Activation of the extended diagnostics
The extended diagnostics is deactivated at the factory, parameter 51 is
therefore at "OFF". There are three operating modes for activating the
extended diagnostics:
On1: The extended diagnostics is activated and the threshold 3
S
error messages are also output via the fault message output.
On2: The extended diagnostics is activated, the threshold 2 error
S
messages are output via alarm output 2 and the threshold 3 error
messages are also output via fault message output.
On3: The extended diagnostics is activated, the threshold 1 error
S
messages are output via alarm output 1, the threshold 2 error
messages are output via alarm output 2 and the threshold 3 error
messages are also output via the fault message output.
NOTE
Please note that the menu items of the extended diagnostics from
A. PST to P. PAVG are only displayed in the display after selecting
one of the three On operating modes.
With the factory setting, the parameters of menu items A to P are
deactivated by default (OFF). The corresponding parameters are only
displayed once you have activated the relevant menu item with "On".
Operation
109