3.3.6 Assembly procedure (see figure 3-8 and figure 3-9)

SIPART PS2 Manual
A5E00074631--06
1.
Attach VDI/VDE 3845 mounting console ((9), actuator-specific,
scope of delivery actuator manufacturer) onto rear of positioner
and secure using hexagon head screws (14) and lock washers
(15).
2.
Adhere pointer (4.2) onto mounting console in the center of the
centering hole.
3.
Push the coupling wheel (2) onto positioner axis, pull back by
about 1 mm and tighten the hexagon socket head screw (18) with
the Allen key provided.
4.
Place the carrier (3) onto the end of the actuator and secure using
Fillister head screw (16) and washer (17).
5.
Carefully place positioner with mounting console onto the actuator
such that the pin of the coupling wheel engages in the actuator.
6.
Align the positioner/mounting console assembly in the center of the
actuator and screw tight.
(Screws not included in delivery; they are part of the actuator
mounting console!)
7.
Following startup as described in Chapter 3.6, page 72: Drive the
actuator to the end position and adhere scale (4.1) on the coupling
wheel (2) according to direction of rotation and part-turn actuator.
The scale is self--adhesive!
Preparing for Operation