Connection

5.1

Lightning protection, power supply and grounding

Notes on lightning protection
Danger due to lightning strikes
Antennas installed outdoors must be within the area covered by a lightning protection
system. Make sure that all conducting systems entering from outdoors can be protected by
a lightning protection potential equalization system.
When implementing your lightning protection concept, make sure you adhere to the VDE
0182 or IEC 62305 standard.
Suitable lightning protectors are available in the range of accessories of SIMATIC NET
Industrial WLAN:
● Lightning protector LP798-1N (order no. 6GK5798-2LP00-2AA6)
● Lightning protector LP798-2N (order no. 6GK5798-2LP10-2AA6)
Note
We recommend that you use the maintenance-free lightning protector LP798-2N.
Exception:
When there is also DC power is supplied via the antenna cable. In this case, only the
lightning protector LP798-1N can be used.
Danger due to lightning strikes
Installing this lightning protector between an antenna and a SCALANCE W700 is not
adequate protection against a lightning strike. The LP798-1N lightening protector only
works within the framework of a comprehensive lightning protection concept. If you have
questions, ask a qualified specialist company.
SCALANCE W788C-2
Operating Instructions, 11/2014, A5E03692120-07
WARNING
WARNING
5
19