Warning and alarm messages
There is a clear distinction between alarms and
warnings. In the case of an alarm, the FCM 300/FCD
300/VLT 2800 will enter a fault condition. After the
cause for the alarm has been cleared, the master will
have to acknowledge the alarm message for the FCM
300/FCD 300/VLT 2800 to start operating again. A
warning, on the other hand may come when a warning
condition appears, and disappear when conditions
return to normal without interfering with the process.
Warnings
Any warning within the FCM 300/FCD 300/VLT
2800 is represented by a single bit within a warning
word. A warning word is always an active parameter.
Bit status FALSE [0] means no warning, while bit
status TRUE [1] means warning.
Any bit change in the warning word will result in a
Spontaneous message being issued.
In addition to the warning word message the
master will also be notified through a change
of bit 7 in the Status Word.
Alarms
Following an Alarm message the FCM 300/FCD
300/VLT 2800 will enter Fault condition. Only
after the fault has been alleviated and the master
has acknowledged the alarm message by setting
bit 7 in the Control word, can the FCM 300/FCD
300/VLT 2800 resume operation.
Any alarm within the FCM 300/FCD 300/VLT
2800 is represented by a single bit within an
alarm word. An alarm word is always an action
parameter. Bit status FALSE [0] means no fault,
while bit status TRUE [1] means fault.
Any bit change in the alarm word will result in a
Spontaneous message being issued.
Spontaneous messages
If a fault or warning condition should occur, the
FCM 300/FCD 300/VLT 2800 will, if the proper
communicative relationship has been established, issue
a Spontaneous message to communication partners.
Instead of responding to the master's request, the FCM
300/FCD 300/VLT 2800 will exchange the requested
response with the alarm or the warning message.
Warnings and alarms will trigger a Spontaneous
message. The same is true with any change
to an active parameter.
MG.90.A5.02 - VLT is a registered Danfoss trademark
FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
Warning word, extended Status word and
Alarm word
Warning word, extened status word and alarm word
are shown on the display in Hex format. If there are
more than one warning or alarm, a sum of all warnings
or alarms will be shown. Warning word, extened status
word and alarm word can also be displayed using the
serial bus in parameter 540, 541 and 538.
Bit (Hex)
Alarm word (p. 538)
00000002
Trip lock
00000004
AMT tuning fail
00000040
HPFB timeout
00000080
Standard bus timeout
00000100
Short circuit
00000200
24 V cupply fault
00000400
Earthe fault
00000800
Overcurrent
00002000
Motor thermistor
00004000
Motor overload
00008000
Inverter overload
00010000
Undervoltage
00020000
Overvoltage
00040000
Phase loss
00800000
Live zero error
01000000
Heat sink temperature too high
02000000
Profibus communication fualt
08000000
Inrush fault
10000000
Internal fault
Bit (Hex)
Alarm word (p. 540)
00000008
HPFB timeout
00000010
Standard bus timeout
00000040
Current limit
00000080
Motor thermistor
00000100
Motor overload
00000200
Inverter overload
00000400
Undervolt
00000800
Overvolt
00001000
Voltage warning low
00002000
Voltage warning high
00004000
Phase loss
00010000
Live zero error warning
00400000
Out of frequency range
00800000
Profibus communication fault
40000000
Switch mode warning
80000000
Heat sink temperature high
39