is still possible via the terminals, depending on how
the parameters 502-508 have been programmed.
953 Warning parameter 1
(WARN. PARA)
Value:
Read only
Function:
In this parameter it is possible to read out warning
messages via standard bus or Profibus. This
parameter is not available via LCP, but the warning
message can be seen by choosing Com warning
word as display readout. A bit is assigned to
every warning (see the following list).
Bit
Bit = "1" when:
0 LSB
Connection with DP-master is not ok
1
Not used
2
FDL (Field-bus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Spontaneous message FIFO overflow
6
PROFIBUS ASIC is not transmitting
7
Initialising of PROFIBUS option is not ok
8
Not used
9
Not used
10
Not used
11
Not used
12
Fatal DPR-handling error/Error code
during init.: Bit 0
13
Fatal DPR-handling error/Error code
during init.: Bit 1
14
Fatal DPR-handling error/Error code
during init.: Bit 2
15 MSB Fatal DPR-handling error/Error code
during init.: Bit 3
Explanation of error codes:
Depending of Bit 7 the corresponding error codes
can be seen from Bit 12-15.
Bit 7 = 1: Initialisation failure
Code
0
OK
1
Init. channel not empty
2
No resp. on command "Init. SPC3
controller"
3
No resp. on command "No action"
4
No resp. on writing init.-data
5
No valid resp. on writing init.-data
6
No positive resp. on writing init.-data
36
FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
Bit 7 = 0: Run time failure
Code
0 OK
1 Fatal error in warning channel
2 Fatal error in spontaneous channel
3 Fatal error in channel for input of process
data
4 Fatal error in channel for output of process
data
5 Fatal error in parameter channel 1
6 Fatal error in parameter channel 2
7 Fatal error in parameter channel 3
15 Fatal error in DPR form SPC3
964 Identification
Value:
0 Manufucturer
1 Device type
2 Version
3 Firmware date year
4 Firmware date month
5 Number of axes
6 Profibus version
7 Database Version
8 Power unit ID
9 BMC software ID (P632)
Function:
This parameter contains the identification of a Profibus
slave. This parameter is read only and only accessible
via the Profibus V1 communication.
965 Profile Number
(PROFILE NUMBER)
Value:
Profile number 1. octet Manufucturer
Profile number 2. octet
Function:
This parameter contains the profile number which a
Profibus slave supports. This parameter is read only
and only accessible via the Profibus V1 communication.
MG.90.A5.02 - VLT is a registered Danfoss trademark
[3]
[3]