August 2018
Message: Enter text up to 32 characters long. The Message is blank by
default, does not display if left blank, and may be used for any purpose.
Date: Enter a date in mm/dd/yyyy format. The date may be used for any
purpose, such as recording the date of the most recent calibration.
3. When finished making changes, select Send to update the device
configuration.
8.0

Wireless considerations

8.1
Power up sequence
The Rosemount
be installed only after the Wireless Gateway has been installed and is
functioning properly. Install the Emerson
the Rosemount 928 Wireless Gas Monitor to power the device. Power up
Wireless devices in order of proximity from the Gateway, beginning with the
closest. This results in a simpler and faster network installation. Enable Active
Advertising on the Gateway to ensure that new devices join the network faster.
Refer to the reference manual for your Wireless Gateway for more information.
8.2
Antenna position
The antenna should be positioned vertically, either straight up or straight down
and should be, if the application requirements allow, approximately 3 ft. (1 m)
from any large structure, building, or conductive surface to allow for clear
communication with other devices.
928 Wireless Transmitter and all other wireless devices should