Emerson Rosemount 644 HART Reference Manual page 58

Temperature transmitter, for product shipped before september 2012
Table of Contents

Advertisement

Hardware Installation
July 2016
8. Connect the shielded power cable leads to the transmitter power terminals. Avoid contact with
sensor leads and sensor connections. Connect and tighten the cable gland.
9. Install and tighten the connection head cover. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
A
A. Connection head cover
B. Connection head
C. Thermowell
Typical Universal Head Installation–head mount transmitter with
threaded sensor
1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before
applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell. Seal the nipple and adapter
threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for severe environments or to
satisfy code requirements.
4. Verify the transmitter failure mode switch is in the desired position.
5. Pull the sensor wiring leads through the universal head and transmitter. Mount the transmitter in the
universal head by threading the transmitter mounting screws into the universal head mounting holes.
6. Seal adapter threads with thread sealant.
7. Pull the field wiring leads through the conduit into the universal head. Wire the sensor and power
leads to the transmitter (see
other terminals.
8. Install and tighten the universal head cover. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
48
B
E
D
"Wiring and powering the transmitter" on page
F
D. Rosemount 644 Transmitter
E. Integral mount sensor with flying leads
F. Extension
Reference Manual
00809-0100-4728, Rev MB
C
64). Avoid contact with
Hardware Installation