Installation Instructions for Type 1MM, 3MM, 35MM, 37MM,
35SS, and 37SS Modular Metering Centers
H A Z A R D O U S V O LTA G E . W I L L C A U S E
SEVERE I NJURY OR DEATH.
Tu r n O F F p owe r s u p p l y i n g t h i s e q u i p m e n t b e fo r e wo r k i n g
inside.
T E N S I O N DA N G E R E U S E . P E U T C AU S E R
D E S B L E S S U R E S G R AV E S O U L A M O RT.
Co u p e r l 'a l i m e n t a t io n é l e c t r iq u e de c e t é quip e m e n t avan t
d'y effect uer de s travaux.
VO LTA J E P E L I G R O S O. C AU S A H E R I DA S
SEVERAS O MUE RTE.
INTERRUMPA el s umini stro de energia que alime nta e ste
e q u i p o a n t e s d e t r a b a j a r e n e l i n t e r i o r d e l m i s m o .
INSTALL MOUNTING RAILS ON WALL:
Establish the required height of the centerline of the bottom
meter socket, per the utility company specifications.
Determine the bottom line of the meter modules and main
devices. Use a "Z" dimension per the table below. That
is the distance from the bottom meter socket line to the
bottom of a meter module.
Measure up a distance "X" (see table) inches from the
bottom line of the meter modules to mounting holes for the
mounting rail. Strike a level line for the fasteners and attach
the mounting rails. (See Fig. 1 below).
MOUNTING FEET
MOUNTING RAIL(S)
MOUNTING FEET
TYPE OF METER MODULE
1MM, 3MM - 125 AMP
1MM, 3MM - 200 AMP
35SS, 37SS - 1 METER
35SS, 37SS - 2,3 METER
35MM, 37MM - 1,3,4 METER
35MM, 37MM - 2 METER
Fig. 1 Locations of Mounting Feet, Rails, and Modules
I.L. 70-8306
DANGER
)
PELIGRO
MAIN DEVICE
"X" in.(mm)
"Z" in.(mm)
34-7/32 (869.16)
12-19/32 (319.88)
34-7/32 (869.16)
18-15/32 (469.11)
17-1/16 (433.39)
19-27/32 (504.03)
35-3/16 (893.76)
18-1/2 (469.90)
30-11/16 (779.46)
13 (330.20)
30-11/16 (779.46)
27 (685.80)
Please read these instructions completely before installing
or removing device. Improper installation could be
hazardous to personnel and/or equipment.
Por favor lea estas instrucciones en su totalidad antes de
instalar o mover el aparato. Una instalacion inapropiada
puede ser peligrosa para el personal y/o el equipo.
Veuillez lire les présentes directives au complet avant
d'installer ou de retirer le dispositif. Une mauvaise installation
pourait causer des blessures au personnel et/ou
endommager l'equipement.
MOUNTING FEET:
Swivel the mounting feet at the top and bottom of the en-
closures as shown (meter modules have two mounting feet
and main devices have four mounting feet). After marking
holes on the wall, the mounting feet may be moved away
for drilling of the holes. (See Fig. 1 below).
METER SOCKET COVERS:
Remove all the meter socket covers which are over the
horizontal main bus. Ring style covers are attached with
two screws inside the socket rim. Ringless style covers
are attached with an external movable latch. (See Fig. 2).
Ringless style covers have barrel lock provision K.O. To
use, remove knockout and apply kit 3MMBLKIT or 37MMBLK.
MOVABLE LATCH
METER COVER
SCREWS
RING STYLE
COVER
RINGLESS STYLE
Fig. 2 Ring Type and Ringless Covers
METER MODULES:
Hang meter modules on the mounting rails, loosen all of
the main bus joint bolts, and slide the meter modules
together.
Fasten the enclosures together, in order to bond devices
together and provide suitable ground path, with the (2) #
20 screws supplied with each module.
Torque to 26 lb-in (2.94 N-m).
Torque each main bus joint bolt to 300 lb-in (33.90 N-m).
Secure mounting feet to the wall. (See Fig. 3 on Page 2).
COVER
-
1

Advertisement

loading

Summary of Contents for Eaton 1MM

  • Page 1 Installation Instructions for Type 1MM, 3MM, 35MM, 37MM, 35SS, and 37SS Modular Metering Centers DANGER Please read these instructions completely before installing or removing device. Improper installation could be H A Z A R D O U S V O LTA G E . W I L L C A U S E hazardous to personnel and/or equipment.
  • Page 2 PROVISIONS FOR HUBS OR KNOCKOUTS: KNOCKOUT PLATE - Top Connections - Outdoor Application (1MM & 3MM) Fig. 4 Knockout Locations and Phase Connections Knockouts are not provided in top endwall. Punch proper holes as required. Install raintight hubs on outdoor PHASE BALANCING, 3 PHASE SYSTEM (3MM ONLY): devices.
  • Page 3 Notice d’installation des centres de comptage modulaires de type C3MM. INSTALLATION DES RAILS DE MONTAGE SUR LE MUR: COUVERCLES DES EMBASES DE COMPTEUR: Établir la hauteur appropriée á partir de la ligne médiane de Enlever tous les couvercles des embases de compteur qui l’embase du comteur du bas, conformément aux spécifications recouvrent la barre horizontale principale.
  • Page 4 PLACA DE AGUJERO CIEGO BOULONS SUPERIOR O PLACA POUR JOINTS CHAPEAU HIDRÓFUGA BARRE PRINC. D’EXTRÉMITÉ AFFLEURANT DISPOSITIF CHAPEAU PRINCIPAL DISPOSITIF D’EXTRÉMITÉ PRINCIPAL EN SAILLIE PLAQUE Á L’ÉPREUVE DE LA PLUIE CONNECTEURS DE PHASE VIS Nº - 20 ET PLAQUE INFÉRIEURE AVEC Fig.

This manual is also suitable for:

37mm3mm35ss35mm37ss