11-4-2 Caution at Servicing
1. After using the service mode of remote controller finished, press the [
normal function.
2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air
conditioner to normal operation. However, the check codes are not deleted from memory of the microcomputer.
3. After servicing finished, press [CLR] button of remote controller under service mode status to send code "7F" to the
indoor unit. The check code stored in memory is cleared.
Block distinction
Check
Block
code
Indoor P.C.
board.
Operation of diagnosis function
Check
Cause of operation
code
TA sensor ; The room
temperature sensor is
short-Circuit or disconnection.
TC sensor ; The heat
exchanger temperature
sensor of the indoor unit
is out of place, disconnection,
short-circuit or migration.
Fan motor of the indoor unit
is failure, lock-rotor, short-
circuit, disconnection, etc.
Or its circuit on P.C. board
has problem.
Other trouble on the indoor
P.C. board.
] button to reset the remote controller to
Table 11-4-1
Air
Display flashing
conditioner
error
status
Operation
Flashes when
continues.
error is detected. 2. In case of the sensor and its
Operation
Flashes when
continues.
error is detected. 2. In case of the sensor and its
All OFF
Flashes when
error is detected. 2. In case of the motor and its
Depend on
Depend on
cause of
cause of
failure.
failure.
- 69 -
FILE NO. SVM-18048
Action and Judgment
1. Check the sensor TA and connection.
connection is normal, check the
P.C. board.
1. Check the sensor TC and connection.
connection is normal, check the
P.C. board.
1. Check the fan motor and connection.
connection is normal, check the
P.C. board.
Replace P.C. board.