Exchangers Pressure Drop (Ft) - Baxi LUNA HT 1.450 Installation And Servicing Instructions

Condensing gas fired wall hung boiler
Table of Contents

Advertisement

Available languages

Available languages

2.7 EXCHANGERS PRESSURE DROP
The electrical specifications of the pump must be as follows:
- 120 V AC; 60 Hz; 10µF; 0.82 A cos f 0.9.
Note:
If the specifications of the installed pump are different, a relay must be wired between the boiler control circuit board
and the pump.
The minimum water flow rate must be as follows:
* HT 1.450 = 3.7 gpm
* HT 1.650 = 4.4 gpm
with a central heating water pressure between 1 and 1.5 bar (14.5 and 21.7 psi).
Graph 1
INSTALLATION AND SERVICING INSTRUCTIONS
7110242.02 - en
9