P2000 - Maximum RPM
Sets the maximum motor RPM.
Calculate P2000 value using this equation or use the examples:
Imperial: design speed X 47.28702
Metric: design speed X 9308.468
Design Speed
ft/min
10
22
35
1
50
1.
factory default
1. Set S110 display to drive number 02 (see
2. Use
3. Press
4. Press
5. Use
6. Press
7. Press
P0977 - Save to Micro Memory Card (MMC)
Saving the application settings to the MMC will ensure quick recovery in case of power
loss.
1. Set S110 display to drive number 01 (see
2. Use
3. Press
4. Press
5. Use
7ML19985MN01
SITRANS WW100 - OPERATING INSTRUCTIONS
m/sec
P2000
0.05080
472.870
0.11176
1040.31
0.17780
1655.05
0.25400
2364.351
or
arrows to navigate to P2000.
so the current parameter value is displayed.
to activate edit mode (display will flash).
and
to set the value (calculated above).
to acknowledge the new value (display will stop flashing).
again and hold for 3 seconds to save.
or
arrows to navigate to P0977.
so the current parameter value is displayed.
to activate edit mode (display will flash).
and
to set the value to 1.
Switch drives on page 10
Switch drives on page 10
).
).