SystemAir Topvex SX/C Series Installation Instructions Manual
SystemAir Topvex SX/C Series Installation Instructions Manual

SystemAir Topvex SX/C Series Installation Instructions Manual

Air handling unit
Hide thumbs Also See for Topvex SX/C Series:

Advertisement

Topvex SX/C, Topvex TX/C
Air Handling Unit
GB
Installation instructions
Document in original language | 151621 · A002

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Topvex SX/C Series and is the answer not in the manual?

Questions and answers

Summary of Contents for SystemAir Topvex SX/C Series

  • Page 1 Topvex SX/C, Topvex TX/C Air Handling Unit Installation instructions Document in original language | 151621 · A002...
  • Page 2 © Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. 151621 | A002...
  • Page 3: Table Of Contents

    Contents EU Declaration of Conformity ......1 Warnings............2 Product information .........2 General ..........2 Technical data ........3 3.2.1 Dimensions and weight Topvex SX/C ......3 3.2.2 Dimensions and weight Topvex TX/C ......4 3.2.3 Electrical data ......6 Transport and storage ......7 Installation.............7 Unpacking ..........7 Where/how to install ......7 Condensation drain.........8 Installing the unit........9...
  • Page 5: Eu Declaration Of Conformity

    EU Declaration of Conformity | EU Declaration of Conformity Manufacturer Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com hereby confirms that the following products: Air handling units Topvex SX/C and Topvex TX/C...
  • Page 6: Warnings

    Product information General This installation manual concerns air handling unit type Topvex SX/C, TX/C manufactured by Systemair Sverige AB. The units include the following model options: • Model: Topvex SX/C03, Topvex SX/C04, Topvex SX/C06, Topvex TX/C03, Topvex TX/C04 and Topvex TX/C06.
  • Page 7: Technical Data

    Product information | Technical data 3.2.1 Dimensions and weight Topvex SX/C 1063 1063 Model 1041 1772 1926 Topvex SX/C03 1127 1905 2060 Topvex SX/C04 1412 2187 2344 Topvex SX/C06 SX/C06 has 4 extra feet Model Weight, kg Topvex SX/C03 Topvex SX/C04 1120 Topvex SX/C06 151621 | A002...
  • Page 8: Dimensions And Weight Topvex Tx/C

    | Product information 3.2.2 Dimensions and weight Topvex TX/C Fig. 1 Dimensions (mm) Topvex SX/C03 (drawn as left hand unit) Model 1587 1210 1435 Topvex TX/C03 Model ØM Weight, kg Topvex TX/C03 151621 | A002...
  • Page 9 Product information | Fig. 2 Dimensions (mm) Topvex TX/C04-06 drawn as left hand unit Model 1860 1279 1708 Topvex TX/C04 2150 1630 1998 Topvex TX/C06 TX/C has 4 extra feet Model Weight, kg Topvex TX/C04 Topvex TX/C06 1065 151621 | A002...
  • Page 10: Electrical Data

    | Product information 3.2.3 Electrical data Model Fans (W tot.) 230V 1~ El Heating battery (kW Fuse (mains) (A) for and 400 V 3N~ tot.) 230 V 1~ and 400 V 1480 3x25 Topvex SX/C03 EL 1480 Topvex SX/C03 None, HWL, HWH 1088 3x25 Topvex SX/C03 EL M0...
  • Page 11: Transport And Storage

    Unpacking Verify that all ordered equipment are delivered before starting the installation. Any deviation from the ordered equip- ment must be reported to the supplier of Systemair products. Where/how to install The unit is meant for indoor installation. The electronic components should not be exposed to lower temperature than 0°...
  • Page 12: Condensation Drain

    | Installation Condensation drain The unit must be connected to the condensation drain, which is enclosed upon delivery. The drainage needs to be con- nected on the exhaust air side of the heat exchanger at the bottom of the unit, figure 3. If the unit is to be used for cool recovery the normally plugged drainage outlet needs to be connected as well to a separate tube and water lock (accessories).
  • Page 13: Installing The Unit

    Installation | Installing the unit The unit is designed for floor installation. Left and right connections are possible. The unit can be installed in the follow- ing positions. Fig. 5 Installing position (left hand units) Fig. 6 Installing position (right hand units) Table 2 Symbol description Symbol Description...
  • Page 14: Installation Procedure

    | Installation 4.4.1 Installation procedure Warning Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing. 1 Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, levelled and that it carries the weight of the unit.
  • Page 15: Connections

    Installation | Connections 4.6.1 Ducting Position Description Symbol Connection supply air Connection exhaust air Connection outdoor air Connection extract air Fan supply air Fan extract air Filter supply air Filter extract air Heat exchanger Electrical connection box Damper by-pass outdoor air Pressure transmitter supply air fan/extract air filter Pressure transmitter extract air fan/supply air filter Re-heater battery...
  • Page 16: Condensation And Heat Insulation

    | Installation 4.6.2 Condensation and heat insulation Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation installation on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier.
  • Page 17: Electrical Connection, Components

    Installation | 4.6.4 Electrical connection, components Danger • Make sure that the mains power supply to the unit is disconnected before performing any maintenance or electrical work! • All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
  • Page 18: External Connections

    | Installation 4.6.5 External connections Table 3 Connections to external functions Terminal block Description Remark Ground Earthed neutral (mains power supply) Used for phase 230V 1~ and 400V 3~ Used for phase 230V 1~ if the Phase (mains power supply) unit has this mains 400V 3~/230V 3~ Phase (mains power supply)
  • Page 19: Bms Connection

    Installation | 4.6.6 BMS Connection Communication possibilities for control unit. • RS485(Modbus): 50-51-52 or 60-61-62 • RS485(BACnet): 50-51-52 or 60-61-62 • RS485(Exoline): 50-51-52-53 or 60-61-62-63 • TCP/IP Exoline • TCP/IP Modbus • TCP/IP WEB • TCP/IP BACnet RS 485 connection Fig.
  • Page 20: Installing Navipad Control Panel

    100 meters of cable. 4.7.1 Dimensions NaviPad is the control panel for Systemair´s Air handling units. NaviPad has an easy to understand menu structure and contains 13 languages. c/cD 40,3...
  • Page 21 Installation | 151621 | A002...
  • Page 22 | Installation 151621 | A002...
  • Page 23 Installation | 151621 | A002...
  • Page 24 Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.com...

Table of Contents