MODEL LD - LARGE DISPLAY TIMER AND CYCLE COUNTER

GENERAL DESCRIPTION

The Large Display Timer and Cycle Counter is a versatile display that
functions as an Elapsed Timer or Preset Timer, with full-featured user
programmability. The meter includes a built-in Cycle Counter, relay output and
serial communications capability. The 6 digit displays are available in either
2.25" or 4" high red LED digits with adjustable display intensity. The 2.25" high
models are readable up to 130 feet. The 4" high models are readable up to 180
feet. Both versions are constructed of a NEMA 4 enclosure in light weight
aluminum.
The Timer has two signal inputs and eight input operating modes. These
modes provide level active or edge triggered start/stop operation. The Timer
features 18 selectable timer ranges to cover a wide variety of timing
applications. The built-in Cycle Counter can be linked to timer operation to
count timing cycles, or function as a totally independent counter, accepting
count speeds up to 500 Hz. The display can be toggled either manually or
automatically between the Timer and Counter values.
In addition to the Timer/Counter inputs, a programmable User Input is
provided to perform a variety of meter functions. DIP switches are used to
configure the inputs for current sinking (active low) or current sourcing (active
high) operation.
The Setpoint Output can be assigned to the Timer or Counter value, and
configured to suit a variety of control and alarm requirements. The meter also
includes jumper selectable RS232 or RS485 serial communications.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
DIMENSIONS In inches (mm)
U
L
C
US LISTED
US LISTED
4
IND. CONT . EQ.
51EB
CAUTION: Risk of electric shock.
! 2.25" or 4" HIGH RED LED DIGITS
! 6-DIGIT BI-DIRECTIONAL TIMING CAPABILITY
! 5-DIGIT CYCLE COUNTING CAPABILITY
! SELECTABLE TIMER RANGES AND OPERATING MODES
! ELAPSED TIMER AND PRESET TIMER FUNCTIONALITY
! SERIAL COMMUNICATIONS (SELECTABLE RS232 or RS485)
! PROGRAMMABLE USER INPUT
! AC OR DC POWERED
! 5 AMP FORM C RELAY OUTPUT
! ALUMINUM NEMA 4X CASE CONSTRUCTION
SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and
corresponding literature, or on equipment, must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment connected to
it. If equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.

SPECIFICATIONS

1. DISPLAY: 2.25" (57 mm) or 4" (101 mm) intensity adjustable Red LED
2. POWER REQUIREMENTS:
AC Power:
AC Input: 85 to 250 VAC 50/60 Hz, 14 VA
DC Out: 11 to 16 VDC @ 50 mA (consult factory for higher current draw)
DC Power:
DC Input: 11 to 16 VDC @ 400 mA max, 7 W
3. TIMER DISPLAY: 6-digits
Display Range: 0 to 999999
Overflow/Underflow Indication: Display flashes "
Minimum Digit Resolution: 0.001 Sec.
Maximum Single Digit Resolution: 1 Hr.
Timing Accuracy: ±0.01%
4. CYCLE COUNTER DISPLAY: 5-digits, may be disabled if not used
Display Designator: "
" to the left side of the display
'
Display Range: 0 to 99999
Overflow/Underflow Indication: Display flashes "
1
Bulletin No. LDT-B
Drawing No. LP0634
Released 9/06
"
! #$%&
"
' #$%&
PART
X (Length)
Y (Height)
NUMBER
LD2T06P0 16 (406.4)
4 (101.6)
LD4T06P0 26 (660.4) 7.875 (200)
Z (Center)
12 (304.8)
22 (558.8)

Advertisement

Table of Contents
loading

Summary of Contents for red lion LD

  • Page 1: General Description

    Released 9/06 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL LD - LARGE DISPLAY TIMER AND CYCLE COUNTER ! 2.25" or 4" HIGH RED LED DIGITS ! 6-DIGIT BI-DIRECTIONAL TIMING CAPABILITY ! 5-DIGIT CYCLE COUNTING CAPABILITY ! SELECTABLE TIMER RANGES AND OPERATING MODES...
  • Page 2: Ordering Information

    Maximum Count Rate: 11. ENVIRONMENTAL CONDITIONS: All Count Sources except Input B: 10 Hz Operating temperature: 0 to 50 °C Input B Count Source: Storage temperature: -40 to 70 °C With Timer Input Filter ON: 10 Hz Operating and storage humidity: 0 to 85% max. RH (non-condensing) With Timer Input Filter OFF: 500 Hz Altitude: Up to 2,000 meters 5.
  • Page 3: Dip Switches

    2.0 S DIP S ETTING THE WITCHES To access the switches, remove the right side plate of the meter. A bank of eight SWITCH 6 (RESET/USER INPUT) {See Note 1} SNK: Adds internal 7.8 KΩ pull-up resistor to +12VDC, I = 2.1 mA.
  • Page 4: Wiring Overview

    WIRING OVERVIEW Electrical connections are made via pluggable terminal blocks located inside the meter. All conductors should conform to the meter's voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
  • Page 5: Input Wiring

    4,000 ft. and data rates as high as 10M baud (the LD is limited to 19.2k baud). The same pair of wires is used to both transmit and receive data. RS485 is therefore always half-duplex, that is, data cannot be received and transmitted simultaneously.
  • Page 6: Factory Settings

    4.0 R EVIEWING THE RONT ANEL EYS AND ISPLAY DISPLAY MODE OPERATION PROGRAMMING MODE OPERATION Access Programming Mode Store selected parameter and index to next parameter Advance through selection list/increment selected digit SEL! ! Select display (Timer or Cycle Counter) of parameter value RST"...
  • Page 7: Parameter Menu

    5.1 MODULE 1 - T IMER NPUT ARAMETERS /0.*( PARAMETER MENU TIMER INPUT FILTER TIMER RANGE :.-!%& &2*3% 18 TIMER RANGE SELECTIONS " " = SEC; = MIN; = HR; = DAY 111111 Provides a 50 msec software debounce for the Timer Inputs (A and B). Select RANGE MAXIMUM DISPLAY...
  • Page 8 TIMER RESET AT POWER-UP USER INPUT FUNCTION (Cont’d) & (0<( DISPLAY MODE DESCRIPTION Inhibit timing or counting for the " Inhibit .>B=@! selected value(s). Display Intensity Level Increase intensity one level The Timer can be programmed to Reset at each meter power-up. 50-%$ (Edge Triggered) for each activation.
  • Page 9 5.3 MODULE 3 - D ISPLAY AND RONT ANEL ARAMETERS 905+( PARAMETER MENU the Setpoint values and Timer Stop value to be modified, but allows direct FRONT PANEL DISPLAY SELECT ENABLE (SEL access to these values without having to enter Full Programming mode. +%-0%>...
  • Page 10 5.4 MODULE 4 - S ETPOINT UTPUT ARAMETERS D0+(! PARAMETER MENU Module 4 is the programming module for the Setpoint Output parameters. SETPOINT OUTPUT TIME-OUT Some parameters will not appear depending on the Setpoint Assignment and #0!#<! Setpoint Output Action selected. ;;, ;...
  • Page 11 5.5 MODULE 5 - S ERIAL OMMUNICATIONS ARAMETERS 10+%& PARAMETER MENU Module 5 is the programming module for the Serial Communications Parameters. These parameters are used to match the serial settings of the meter ABBREVIATED PRINTING with those of the host computer or other serial device. 2@@&...
  • Page 12 Sending Serial Commands and Data Register Identification Chart When sending commands to the meter, a string containing at least one command character must be constructed. A command string consists of a Applicable Value Description MNEMONIC Transmit Details (T and V) Commands command character, a value identifier, numerical data (if writing data to the meter) followed by a command terminator character, * or $.
  • Page 13 ). Each ASCII character is “framed” with a beginning start bit, receiving device. The LD Timer ignores the parity bit of incoming data and sets an optional parity bit and one or more ending stop bits. The data format and the parity bit to odd, even or none (mark parity) for outgoing data.
  • Page 14 This page intentionally left blank.
  • Page 15 LD TIMER PROGRAMMING QUICK OVERVIEW...
  • Page 16: Limited Warranty

    The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products...

Table of Contents