Settings - Siemens SIPROTEC 4 7VE61 Manual

Multifunction paralleling
Table of Contents

Advertisement

Functions
2.2 Paralleling Functions
PAUSE. If the parameter 6182 T U PULS MAX is set to ∞ there is no time restriction and a continuous pulse is
output until the calculated time has expired.
In particular with hydro-electric power stations, generator rotation speed can be subject to fluctuations.
Actuator commands established from a current frequency value could thus be incorrect. The option is there-
fore provided using the parameter 6186 SMOOTHING f of subjecting the frequency difference to an aver-
aging with different smoothing factors 1 to 10.
If the frequency difference is Δf ≈ 0 i.e. the generator runs in synchronism with the power system but the
connection conditions are not yet fulfilled, synchronization would not be possible or would take a very long
time. In such cases a "kick impulse" can be issued if the parameter 6187 KICK PULSE = ON was selected and
kick impulses thus enabled. These are issued only if the duration until synchronism exceeds an adjustable time
set by parameters 6189 T SW-ON MIN. This insures that kick impulses are not issued immediately before
synchronism is achieved, but only if the voltage vectors are not coinciding in the immediate future. For the set
value of the parameter 6189 applies the formula: T SW-ON MIN ≈ 1/(2·Δf). The highest of the both set values
of the parameter 6132 df ASYN f2>f1 and 6133 df ASYN f2<f1 are selected for Δf.
The kick impulse is initiated in the direction of the parameter setting from Δf KICK (according to the positive
or negative signs of the frequency value). Its length is calculated from the frequency change df2/dt and the set
value of the parameter 6188 Δf KICK.
2.2.2.2

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
6101
Synchronizing
6102
SyncSD
6103
Umin
6104
Umax
6105
U<
6106
U>
6107
SYNC U1<U2>
6108
SYNC U1>U2<
6109
SYNC U1<U2<
6111A
TSUP VOLTAGE
6112
T-SYN. DURATION
6113
PHASE SEQUENCE
6120
T-CB close
6121
Balancing U1/U2
6122A
ANGLE ADJUSTM.
6124
VT Un1, primary
6125
VT Un2, primary
6126
Unom SECONDARY
6127
T CLS CMD MIN
76
Setting Options
ON
OFF
(Einstellmöglichkeiten
anwendungsabhängig)
20 .. 125 V
20 .. 140 V
1 .. 60 V
20 .. 140 V
YES
NO
YES
NO
YES
NO
0.0 .. 60.0 sec
0.01 .. 1200.00 sec
NO
L1 L2 L3
L1 L3 L2
10 .. 1000 ms
0.50 .. 2.00
0 .. 359 °
0.10 .. 999.99 kV
0.10 .. 999.99 kV
80 .. 125 V
0.01 .. 10.00 sec
Default Setting
Comments
OFF
Synchronizing Function
none
synchronizable switching device
90 V
Minimum voltage limit: Umin
110 V
Maximum voltage limit: Umax
5 V
Threshold U1, U2 without voltage
80 V
Threshold U1, U2 with voltage
NO
ON-Command at U1< and U2>
NO
ON-Command at U1> and U2<
NO
ON-Command at U1< and U2<
0.1 sec
Supervision time Dead Line / Dead
Bus
1200.00 sec
Maximum duration of
synchronism-check
NO
Phase sequence check
2147483647 ms
Closing (operating) time of CB
1.00
Balancing factor U1/U2
0 °
Angle adjustment (transformer)
15.75 kV
VT nominal voltage U1, primary
15.75 kV
VT nominal voltage U2, primary
100 V
Rated Secondary Voltage (Ph-Ph)
0.10 sec
Min close command time of the
CB
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017