E.2 Settings
Addr.
Parameter
4502
df1/dt >/<
4503
STAGE df1/dt
4504
STAGE df1/dt
4505
T df1/dt
4506
df1/dt & f1
4507
df2/dt >/<
4508
STAGE df2/dt
4509
STAGE df2/dt
4510
T df2/dt
4511
df2/dt & f2
4512
df3/dt >/<
4513
STAGE df3/dt
4514
STAGE df3/dt
4515
T df3/dt
4516
df3/dt & f3
4517
df4/dt >/<
4518
STAGE df4/dt
4519
STAGE df4/dt
4520
T df4/dt
4521
df4/dt & f4
4522
U MIN
4523A df1/2 HYSTERES.
4524A df1/2 M-WINDOW
4525A df3/4 HYSTERES.
4526A df3/4 M-WINDOW
4527
MEAS. INPUT
4601
VECTOR JUMP
4602
DELTA PHI
262
Function
Setting Options
df/dt Protect.
-df/dt<
+df/dt>
df/dt Protect.
0.1 .. 10.0 Hz/s
df/dt Protect.
0.1 .. 3.0 Hz/s
df/dt Protect.
0.00 .. 60.00 sec
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
df/dt Protect.
0.1 .. 10.0 Hz/s
df/dt Protect.
0.1 .. 3.0 Hz/s
df/dt Protect.
0.00 .. 60.00 sec
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
df/dt Protect.
0.1 .. 10.0 Hz/s
df/dt Protect.
0.1 .. 3.0 Hz/s
df/dt Protect.
0.00 .. 60.00 sec
df/dt Protect.
OFF
ON
df/dt Protect.
-df/dt<
+df/dt>
df/dt Protect.
0.1 .. 10.0 Hz/s
df/dt Protect.
0.1 .. 3.0 Hz/s
df/dt Protect.
0.00 .. 60.00 sec
df/dt Protect.
OFF
ON
df/dt Protect.
10.0 .. 125.0 V
df/dt Protect.
0.02 .. 0.99 Hz/s
df/dt Protect.
1 .. 25 Cycle
df/dt Protect.
0.02 .. 0.99 Hz/s
df/dt Protect.
1 .. 25 Cycle
df/dt Protect.
Ua
Ub
Uc
Ud
Ue
Uf
Vector Jump
OFF
ON
Block relay
Vector Jump
2 .. 30 °
Default Setting
Comments
-df/dt<
Mode of Threshold (df1/dt
>/<)
1.0 Hz/s
Pickup Value of df1/dt Stage
0.3 Hz/s
Pickup Value of df1/dt Stage
0.50 sec
Time Delay of df1/dt Stage
OFF
AND logic with pickup of
stage f1
-df/dt<
Mode of Threshold (df2/dt
>/<)
1.0 Hz/s
Pickup Value of df2/dt Stage
0.3 Hz/s
Pickup Value of df2/dt Stage
0.50 sec
Time Delay of df2/dt Stage
OFF
AND logic with pickup of
stage f2
-df/dt<
Mode of Threshold (df3/dt
>/<)
4.0 Hz/s
Pickup Value of df3/dt Stage
1.3 Hz/s
Pickup Value of df3/dt Stage
0.00 sec
Time Delay of df3/dt Stage
OFF
AND logic with pickup of
stage f3
-df/dt<
Mode of Threshold (df4/dt
>/<)
4.0 Hz/s
Pickup Value of df4/dt Stage
1.3 Hz/s
Pickup Value of df4/dt Stage
0.00 sec
Time Delay of df4/dt Stage
OFF
AND logic with pickup of
stage f4
65.0 V
Minimum Operating
Voltage Umin
0.10 Hz/s
Reset Hysteresis for df1/dt &
df2/dt
5 Cycle
Measuring Window for
df1/dt & df2/dt
0.40 Hz/s
Reset Hysteresis for df3/dt &
df4/dt
5 Cycle
Measuring Window for
df3/dt & df4/dt
Ua
Used Measuring Input
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA PHI