Service Conditions; Design - Siemens SIPROTEC 4 7VE61 Manual

Multifunction paralleling
Table of Contents

Advertisement

Technical Data
4.1 General

Service Conditions

4.1.8
The protection device is designed for installation in normal relay rooms and plants, so that electromagnetic compatibility
(EMC) is ensured if installation is done properly.
In addition the following is recommended:
Contactors and relays operating within the same cubicle or on the same relay board with digital protection equip-
ment should always be provided with suitable quenching equipment.
For substations with operating voltages of 100 kV and above, all external cables should be shielded with a conduc-
tive shield grounded at both ends. For substations with lower operating voltages, no special measures are normally
required.
Do not withdraw or insert individual modules or boards while the protective device is energized. When handling the
modules or the boards outside of the case, standards for components sensitive to electrostatic discharge (Electro-
static Sensitive Devices) must be observed. They are not endangered when inserted into the case.

Design

4.1.9
Housing
Dimensions
Weight (mass) approx.
In flush mounted housing
7VE61** (Housing size
1
/
)
3
7VE63** (Housing size
1
/
)
2
in surface mounted housing
7VE61** (Housing size
1
/
)
3
7VE63** (Housing size
1
/
)
2
Protection class acc. to IEC 60 529
For surface mounting housing equipment
In flush mounted housing
Front
Rear
For personal protection
202
7XP20
See dimensional drawings, Section
Approx. 5.2 kg
Approx. 7.0 kg
Approx. 9.2 kg
Approx. 12 kg
IP 51
IP 51
IP 50
IP 2x with cover cap
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017