2.14 Auxiliary Functions
2.14.8.3

Settings

Addr.
Parameter
401
WAVEFORMTRIGGER
403
MAX. LENGTH
404
PRE. TRIG. TIME
405
POST REC. TIME
406
BinIn CAPT.TIME
2.14.8.4

Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
30053
Fault rec. run.
2.14.9

Time Setup

The integrated date/clock management enables the exact timely assignment of events e.g., those in the
operational messages and fault messages or in the lists of the minimum/maximum values.
2.14.9.1

Functional Description

The time can be influenced by
internal RTC (Real Time Clock)
external synchronization sources (e.g. DCF77, IRIG B)
external minute pulses via binary input.
NOTE
i
i
Upon delivery of the device the internal clock RTC is always set by default as synchronization source,
regardless of whether the device is equipped with a system interface or not. If the time synchronization is
to use an external source, this must be selected.
The procedure for changing the synchronization source is described in detail in the SIPROTEC 4- System
Description.
The following operating modes can be selected:
No.
Operating Mode
1
Intern
2
IEC 60870-5-103
3
PROFIBUS DP
4
Zeitzeichen IRIG B
5
Zeitzeichen DCF77
6
Zeitzeichen Sync.-Box
7
Impuls über Binäreingang
128
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
0.30 .. 10.00 sec
0.05 .. 5.00 sec
0.05 .. 2.00 sec
0.10 .. 10.00 sec
Type of
Comments
Informa-
tion
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT
Fault recording is running
Description
Internal synchronization using RTC (default)
External synchronization via system interface (IEC 60870-5-103)
External synchronization using PROFIBUS interface
External synchronization using IRIG B
(telegramm format IRIG-B000)
External synchronization using DCF 77
External synchronization using the SIMEAS-Synch.Box time signal
External synchronization with pulse via binary input
Default Setting
Comments
Start w. TRIP
Waveform Capture
10.00 sec
Max. length of a Waveform
Capture Record
5.00 sec
Captured Waveform Prior to
Trigger
2.00 sec
Captured Waveform after Event
10.00 sec
Capture Time via Binary Input
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017