5. Diagnosis for Compressor Synchronism (Outdoor unit malfunction)
Outdoor unit malfunction indicator status
D5
D6
Main detection point:
●If the system pressure is over-high?
●If the working voltage is over-low?
Malfunction diagnosis process:
Synchronism after
energize the unit
and start it
N
If the stop time of
compressor is more than
If the compressor
wire COMP(UVW) is well connected, the
connection sequence forwards to
clockwise direction?
N
Connect
wire well
control board
Y
malfunction?
58
D16
D30
3min
Y
Y
Replace
AP1
Remove
N
Replace
compressor
End
Synchronism
occurred during
operation
If the outdoor fan works
N
normally?
Y
If the radiating of unit is
Y
well?
N
If the input voltage of unit
N
is normal?
Y
If the refrigerant is too
Y
much?
N
Replace
control board
AP1
Remove
malfunction?
N
Replace
compressor
End
Check if the fan
terminal OFAN is
connected well
Improve the radiating
of unit (clean heat
exchanger and
increase ventilation)
Start to run until the
power resume normal
voltage
Charge the
refrigerant with
service manual
Y
Installation and Maintenance
Service Manual
Replace fan
capacitor C1
Replace
outdoor fan