GRM SERIES GAS FRYERS
Adjustable Casters (4) two locking, two non-locking for freestanding fryers.
Drain Pipe Extension for freestanding fryers only.
Twin Fry Basket (2) per fry tank.
Cleanout Rod
Crumb Scoop
Manual and Warranty – Retain for future reference.
Do not use the door or its handle to lift the fryer.
Before installing the fryer, verify that the type of gas (natural or propane) agrees with the
specifications on the fryer data plate, which is located on the inside of the door panel. Make
sure the fryer is configured for the proper elevation.
Record your fryer model, device, and serial numbers for future reference in the space
provided below. This information can be found on the fryer data plate.
Fryer Model No: ___________________________
Device:___________________________________
Serial No: ________________________________

Clearances

Minimum clearance from combustible construction:
6" (15 cm) from the sides of the fryer
6" (15 cm) from the back of the fryer
The fryer may be installed on combustible floors
Minimum clearance from noncombustible construction:
0" from the sides of the fryer
0" from the back of the fryer
Between the fryer and any open-top flame units: 16" (41 cm)
Allow space for servicing and operation.

Location

Install fryer in an area with sufficient air supply for gas combustion at fryer burners.
Do not obstruct the flow of combustion and ventilation air.
Provide adequate clearance for air openings into the combustion chamber.
Do not permit fans to blow directly onto fryer.
VULCAN-HART

INSTALLATION

-5-
F-45385 Rev. C (9-15)