P839 TVT Hover Level
Defines (in percent) how high the TVT curve is placed above the profile, relative to the
largest echo. When SITRANS Probe LU is located in the center of the vessel, lower this
parameter to prevent multiple echo detections.
Values

Diagnostic Tests (P900 to P924)

P900 Software Revision Number
Displays the software revision level.
Values (view only)
Secondary index
1.
Select P900.
2.
The secondary index number is visible in the auxiliary reading field.
3.
Press DISPLAY
reading field goes blank).
4.
Key in the index number required, and press ENTER
5.
The software revision level associated with the new secondary index appears.
6.
Press DISPLAY
desired parameter.
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
Range
Default
Range
0.00 to 99.99
1
Main code revision
2
Primary boot revision
3
Alternative boot revision
4
Hardware stack revision
Default
Determined by the software revisions installed
twice to focus control on the secondary index (the auxiliary
twice and use the ARROW keys or enter the value for the next
0 to 100%
33 (%)
.
Page 63