Communications (P799)

P799 Communications Control
Enables the read/write access to parameters via remote communications.
Values
Notes:
• P799 controls the access if you are using a HART master.
• P000 controls the lock access if you are using the Siemens handheld programmer.

Echo Processing (P800 to P825)

The following parameters are for authorized Siemens Service personnel or technicians
familiar with Siemens echo processing techniques. View the echo profile first, before
attempting to modify these parameters.
P800 Near Blanking
Defines the distance from the transducer face to be ignored by the transmitter/receiver.
Values
Related
To extend the blanking beyond the minimum default, enter a value in the units selected in
P005.
1.
For more details, see
Page 56
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
0
Read only
1
*
Read/write
2
Restricted access – read only except for P799 which is read/write
1
Range
(depends on model)
Default
P006 Empty
P007 Span
P838 Auto False-Echo Suppression Distance
Blanking Distance
0.000 to 6.000 m (20 ft) or
0.000 to 12 m (40 ft)
(units selected in P005)
0.250 m (0.820 ft)
on page 89.
A5E32337695