P752 Hart Address - Siemens SITRANS Probe LU Operating Instructions Manual

Ultraschall transmitter
Hide thumbs Also See for SITRANS Probe LU:
Table of Contents

Advertisement

P713 Echo Lock Window
Adjusts the size of the Echo Lock Window. This value is automatically altered when
Measurement Response (P003), Maximum Fill Rate (P700), or Maximum Empty Rate
(P701), are altered.
Values
Altered by
Related Parameters
The Echo Lock Window is a ' d istance window
reading. When a new measurement falls within the window, the window is re-centered
and the new reading calculated. Otherwise, the new measurement is verified by Echo
Lock (P711) before the reading is updated. The distance value of this parameter is given
for a temperature of 20
When the value is 0, the window is automatically calculated after each measurement.
The value is fixed at 0 if Echo Lock (P711) is set to 3.
For slower Measurement Response values (P003), the window is narrow.
For faster P003 values the window becomes progressively wider.
The echo lock window is stored as standard samples, but displayed in units
Note:
based on P005. Any value entered for P713 will be rounded to the nearest sample.

P752 HART address

Note: Accessible via the handheld programmer only by keying in P752.
Sets the device address or poll ID on a HART network. Any address other than 0 will
cause the output current to be a fixed value, and the current will not indicate the reading.
Values
1.
Units are those set in P005.
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
Range
Default
P003 Measurement Response
P005 Units
P711 Echo Lock
o
o
C (68
F).
Range
0 to 15
0.000 to 9999
0.000
1
, centered on the echo used to derive the
Page 55