General Installation Steps

1. Remove existing equipment filter (if present) and clean
blower
compartment:
compartment, since the air cleaner cannot remove accumulated
dirt from the blower chamber and distribution ducts.
2. Leave sufficient room around the air cleaner: There must be
adequate room to remove and replace the filter from the air
cleaner cabinet.
3. Transitions: If the air duct does not fit the air cleaner
opening, a gradual transition is recommended to reduce air
turbulence through the air cleaner and ensure its efficient
operation. A maximum of 20° of expansion, or approximately
4 inches per running foot (10 cm per 30 cm), is
recommended for each side of the transition fitting.
Note: Do not reduce ductwork size to fit a smaller air
cleaner. This will increase the velocity of airflow and may
decrease cleaning efficiency.
4. Turning vanes: If the air cleaner is installed adjacent to an elbow
or angle fitting, field-installed turning vanes are recommended to
improve air distribution across the filter.
5. Remove the door: When remov-
ing or replacing the door, hold the outer
door panel with both hands. The door has
industrial strength magnets in it which
can pinch fingers if caught between door
and cabinet.
Dimensions (in)
MODEL
A
B1
DV15-2117-AB
17.5 21.1 21.7
DV15-2121-AC
21.0 21.1 21.7
DV15-2124-AD
24.5 21.1 21.7
DV15-2814-FA
14.0 28.0 28.6
DV15-2817-FB
17.5 28.0 28.6
DV15-2821-FC
21.0 28.0 28.6
DV15-2824-FD
24.5 28.0 28.6
MODEL
DV15-2117-AB DV15-2121-AC DV15-2124-AD DV15-2814-FA DV15-2817-FB DV15-2821-FC DV15-2824-FD
Airflow - up to
Up to 1200 cfm
maximum rated flow
(2039 m
21 x 17 in
Duct Size
(53 x 43 cm)
0.09 in. w.g.
Pressure Drop*
@ 600 cfm
(Filter Only)
0.26 in. w.g.
@ 1200 cfm
MERV Rating*
Notes:
1. Installation with units with ECM motors recommended.
2. Two filters should be considered for any airflow rates above maximum rated flow or when duct pressure loss is excessive.
Furnace Size
Furnace Riser
AMP-BSRB-2814 AMP-BSRB-2817 AMP-BSRB-2821 AMP-BSRB-2824
When using a furnace riser use DV15-2824-FD on all size furnaces
MERV Rating 15 - Minimum Filtration Efficiency @492 fpm: • E1 85% (0.3 - 1.0 micron) • E2 90% (1.0 - 3.0 microns) • E3 95% (3.0 - 10.0 microns)
*Independent testing performed by LMS Technologies, Inc.
IO-DPAC
Thoroughly
clean
the
blower
B2
C
D
E
F
1.4
0.8
1.3
14.7 19.4
1.4
0.8
1.3
18.2 19.4
1.4
0.8
1.3
21.7 19.4
0.8
0.8
3.8
12.5 23.9
0.8
0.8
3.8
16.0 23.9
0.8
0.8
3.8
19.5 23.9
0.8
0.8
3.8
23.0 23.9
Specifications
Up to 1600 cfm
Up to 1800 cfm
/h)
(2718 m
/h)
(3058 m
3
3
21 x 21 in
21 x 24 in
(53 x 53 cm)
(53 x 61 cm)
0.09 in. w.g.
0.09 in. w.g.
@ 800 cfm
@ 900 cfm
0.29 in. w.g.
0.25 in. w.g.
@ 1600 cfm
@ 1800 cfm
15
15
A
B
www.daikincomfort.com
6. Remove filter: remove filter from cabinet
7. Install
the
cabinet:
furnace and filter riser, air handler or to plenum
with the ten
" x ½" self-tapping hex head screws
8
32
provided. Note direction of flow indicated on top
and bottom of cabinet.
8. Seal the joints in the return air system: All joints and seams
between the air cleaner, the heating / cooling equipment and the
return air duct should be sealed with aluminum tape or mastic to
prevent dust from entering the clean air stream.
9. Replace filter and door: After attaching cabinet and sealing all
joints, reinstall filter (note direction of flow) and replace door,
making sure it is properly seated.
10. Adjust Daikin Badge: If a different orientation is needed, slide
badge up and pull out of door. Rotate to proper orientation
and reinstall.
G
Up to 1200 cfm
Up to 1600 cfm
/h)
(2039 m
/h)
(2718 m
3
3
28 x 14 in
28 x 17 in
(71 x 36 cm)
(71 x 43 cm)
0.08 in. w.g.
0.08 in. w.g.
@ 600 cfm
@ 800 cfm
0.25 in. w.g.
0.24 in. w.g.
@ 1200 cfm
@ 1600 cfm
15
15
C
D
Installation
Attach cabinet to
Up to 2000 cfm
Up to 2000 cfm
/h)
(3398 m
/h)
(3398 m
3
3
28 x 21 in
28 x 24 in
(71 x 53 cm)
(71 x 61 cm)
0.08 in. w.g.
0.06 in. w.g.
@ 1000 cfm
@ 1000 cfm
0.22 in. w.g.
0.17 in. w.g.
@ 2000 cfm
@ 2000 cfm
15
15
Furnace Riser
Furnace
7.5
/h)
3
15
3