200 A 15/25 kV class deadbreak straight connector installation instructions
Step 1
8"
(203 mm)
Bend
neutral
wires down
and out of
the way

Preparation of concentric neutral cable

Step 1
Measure down from top of the cable a minimum of 8" .
Remove cable jacket (if jacketed cable is used) to expose
neutral wires.
Unwind neutral wires.
N
otee:
If an Eaton Cooper Power series jacket seal is used,
follow instructions supplied with the jacket seal kit.
Step 2
Measure down from top of the cable 5 3/4" .
Remove the insulation shield. Take care not to nick or
gouge insulation.
2
installation instructions MN650043EN February 2017
Step 2
Insulation
shield
3
5
/
"
4
(145 mm)
Step 3
1
2
/
8 "
(54.0 mm)
Insulation
Step 3
Measure down from the top of the cable 2 1/8" .
Remove the insulation and conductor shield to expose the
bare conductor. Take care not to nick the conductor.
Place a 1/8" bevel on the insulation to ease installation.
Step 4
If not already in place, apply a suitable jacket seal over the
jacket and exposed neutral wires.
Proceed to Step 5.
Step 4
Conductor
1
/
" Bevel
8
Wire
brush
conductor
Jacket
seal