Toshiba T1000 Series Installation Instructions page 3

4-post rack slide kit
Hide thumbs Also See for T1000 Series:

Advertisement

6. Bolt the Side Rail/Bracket assembly to the 4-Post
Rack using two 1/4"-20 x 5/8" bolts each on the front
and back. Ensure the end with the short adapter
bracket is to the front of the rack. (See Figure 6)
7. Tighten the #8-32 screws used to assemble the Slide
Assembly and Bracket Extenders in Section 4.
8. Repeat step 6-7 for the remaining Side Rail/Bracket as-
semblies. (Figure 7)
6. Install T1000 Modules in Rackmount Slides
CAUTION: Battery Modules weight 150 lb.
(68 kg). Use lifting aids and proper lifting
techniques
NOTE: The T1000 System modules must be arranged top-
to-bottom in the following relative order:
Transformer Module (if present)
Power (UPS) Module
Battery Module w/Output Panel (if present)
Battery Panel w/o Output Panel (if present)
1. Lift the module intended for the bottom slide rail set, and slide the module's E-Z Rails into the extended
Slide Middle Members.
2. Gently slide the module backward until the slides are fully retracted.
3. Repeat steps 1-2 for the module slide rail set immediately above the bottom one.
4. Continue until all modules have been installed on their slide rails.
5. Go to T1000 Installation and Operation Manual - 91074 to continue installation and cabling of the
T1000 System.
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel (713) 466-0277 Fax. (713) 466-8773
US (800) 231-1412 Canada (800) 872-2192 Mexico 01/800/527-1204
www.Toshiba.com/ind
Printed in the U.S.A.
T1000 Series UPS 4-Post Rack Slide Kit Installation Instructions 94034-000
FIGURE 6: INSTALL SLIDE RAIL
ASSEMBLIES IN 4-POST RACK
FIGURE 7: INSTALL REMAINING SLIDE RAIL
ASSEMBLIES IN 4-POST RACK
3