Preset speeds, jog, thread, and external reference inputs are available as standard parameter selections with the EC 2000 control. The EC 2000 uses digital technology to provide a flexible, low noise control for today’s high tech industrial environment. It provides setup and programming via a keypad with a user friendly alphanumeric display;...
Available in panel and NEMA enclosed configurations • Adjustable output voltage from 0 – 90VDC • Up to 8 amps output (see EC 2000 – HP models for higher voltage or current outputs) • Ethernet IP add-on available • Speed (AC tachometer generator or speed pickup) or torque (clutch current) feedback permissible •...
EMI Susceptibility: Complies with IEC 801(1984)-3, class 2. It operates without fault or disturbance under the specified level of radiated EMI (Performance Criteria 1). Enclosures • Available in NEMA Type 1 (Dynamatic Part Number: 015-002000-0300) • Other enclosures available upon request (lead times may vary) Weight •...
SECTION 3 – CONTROL OPERATION MODES Control Modes • Speed (AC Tachometer Generator or Pulse Pickup) • Torque (Current Feedback) • Speed/Torque (switchable) Other Modes of Operation • Local/Remote o Allows the user to switch between keypad use and externally wired devices •...
SECTION 4 – Inputs/Outputs Analog Inputs • Potentiometer/Reference Voltage o Used for setpoints • Automatic Signal o 0-10V, 0-5V, 4-20mA, 8-40mA o Used for setpoints • Motor Current Feedback (AC) • Speed Feedback Digital Inputs • E-Stop (Normally closed) • Stop (Normally closed) •...
Digital Outputs • Run Relay (Normally open) o 2A, 115VAC • Programmable “F” Relay (SPDT) o Speed Mode o Torque Mode o Local Mode o Manual Mode o Auto Mode o Stopped o Stopping o E-Stop o Run o Run 0 o Coasting o Jogging o Fault...
Wiring • Dynamatic recommends adhering to the National Fire Protection Association’s “NFPA 70: National Electrical Code” codes and standards for proper branch protection, SCCR ratings, and ampacity ratings. o https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes- and-standards/detail?code=70 • Terminal Block Tightening Torque o “TB” : 25 lb-in.
There are several 3 contact male pin headers on the board with a jumper either occupying the center and left pins (position A) or the center and right pins (position B). Below is a list of jumper settings for the EC 2000. All jumpers not listed should be left in the default position.
8 – 40 mA (DC) • To properly utilize motor torque limiting with the EC 2000, the red dip switch “SW1” must be set in conjunction with a current transformer. Below is a table with “SW1” contact configurations with Dynamatic® approved current transformers.
SECTION 6 – KEYPAD • The EC 2000 can be either controlled via the keypad or from external pilot device, but initial programming must be done with the keypad. • The keypad is plugged into the “PL2-KEYPAD” male pin header on 15-1200-1.
SECTION 7 – PROGRAMMING Menu A: Control Setup 1. CONTROL TYPE • Speed (default) o Uses the AC Tachometer Feedback for speed feedback and control. • Torque o Clutch coil voltage is regulated. This is frequently used for take-up or spooler applications where torque is proportional to tension and speed varies with the diameter of the roll.
Page 24
6. TORQ PULSES/REV Sets an alternate pulses per revolution rate (PPR) for applications that use more than one transducer. To enable this rate, enable Menu A. Parameter 18 and close TB2-25. 7. CLUTCH MIN RPM The minimum speed for the clutch. 8.
Page 25
(Default: 0). 15. SPEED FILTER CLAMP Limits the amount of speed feedback readings done by the EC 2000. This is primarily used for non-standard speed feedback configurations, noise affected configurations, or heavy loads not getting up to speed in a timely manner (Default: 0).
Page 26
Used to adjust the difference between the actual clutch current (measured with a DC clamp on meter) and the current reading of the EC 2000. If the keypad displayed clutch current is less than measured, increase the percentage, and vice-versa (Default: 100%).
Page 27
26. CONTRLR BAUD RATE Changes the BAUD rate (how fast data is sent over a serial line) of the control data transfer. • 4800 • 9600 (default) • 19200 • 38400 27. DATA XMIT ENABLE Allows the user to enable or disable data transmission. •...
Default: 0% 7. ENABLE CURRENT LOOP The EC 2000 has two PID loops (as seen in the previous parameters), speed and current, where the speed PID loop is fed into the current PID loop. This parameter allows the user to disable the current PID loop.
Allows to user to adjust the brake output (TB1 – B1/B2). Note, the brake will enable when the clutch drops out. For simultaneous clutch and brake output, a “Mutuatrol” modification is required (please consult Dynamatic). 1. Brake Coil Rating Enter the brake current rating found on the nameplate.
If the follower signal is lost or drops below a certain value due to an external failure, the user can program the EC 2000 to run at a specific speed. This parameter allows the user to set the level at which to activate this.
Menu F: ANALOG OUTPUTS The EC 2000 can output two different analog values based on a variety of statuses or setpoints. Note that for a 4-20mA or 8-40mA output, proper programming and a 500 Ohm resistor should be connected (See Figure 10).
Menu G: RELAY OUTPUT 1. F RELAY The F Relay corresponds to TB1- F1/F2/F3 (see Figure 7). Trip ON means the relay is normally deenergized, TRIP OFF means the relay is normally energized. TRIP ON and TRIP OFF have the same options. •...
Menu H: UNITS 1. PROCESS UNITS • RPM (default) • PERCENT (used for torque mode) • USER USER can be selected to display speed in something other than RPM. If chosen, Parameters 2-4 are opened for changing. If not, Parameter 1 is the only one that is open. 2.
Menu J: POTENTIOMTR SETUP The setup menu if an external potentiometer is used for a setpoint reference. 1. POT MINIMUM 2. POT MAXIMUM 3. POT MINIMUM REF 4. POT MAXIMUM REF 7.10 Menu K: SOURCE SELECT The setup menu for run, jog, presets, stop, start, and setpoint reference modes. “TERM” refers to devices attached to TB2, “KEYPAD”...
Page 35
5. PRESET SOURCE Allows the user to change between P1,P2,P3, and P4 on the keypad or through TB2 (see Figure 12). Note: the user changes the programmed presets in “Menu L: PROCESS”. • TERM • KEYPAD 6. PRESET 1 SOURCE Allow the user to change what “P1”...
7.11 Menu L: PROCESS Match minimum and maximum values to previously set values for minimum/maximum speed. 1. MINIMUM PROCESS 2. MAXIMUM PROCESS 3. PRESET 1 The setpoint for “P1”. 4. PRESET 2 5. PRESET 3 6. PRESET 4 7. JOG SETPOINT The setpoint for “JOG”.
Page 37
7. COIL OPEN FLT EN If enabled, the control will fault if there is no detected clutch current when the output voltage is applied. • ENABLE (default) • DISABLE 8. SPD FDBK FLT EN If enabled, the control will fault if there is no detected speed feedback signal (ie AC Tachometer Generator) when the control is trying to run at a set speed.
Page 38
14. UNDERSP FLT EN If enabled, the control will fault if the speed set by parameter 10: UNDERSPEED TRIP is reached. • ENABLE • DISABLE (default) 15. UNDSPD FLT ACTION • RUN (keeps running if an overspeed occurs) • STOP (stops if an overspeed occurs) 16.
7.13 Menu N: AUTO RESTART 1. RESTART POWER EN If enabled, the control will start and enter run mode right after power is applied. • ENABLE • DISABLE (default) 2. RESTART FAULT EN If enabled, the control will restart and enter run mode again after a fault. •...
• Disconnect the clutch coil leads from the EC 2000 (C1 and C2). Try to run the control with a setpoint and measure the DC voltage on the TB1-C1 and C2 (where the clutch coil leads were just connected).
TB2 connections and placing a jumper between TB2-32 and TB2-29. 8.10 SCREEN IS LIT, BUT NOTHING IS DISPLAYED • Try resetting the EC 2000. If the issues persists, check to see if the keypad cable is inserted correctly or not damaged. 8.11 LOCAL/REMOTE KEY DOES NOT WORK •...
SECTION 9 – ETHERNET IP AND SERIAL COMMUNICATIONS The latest major change to the EC 2000 is the implementation of serial communications on the EC 2000 control. The capabilities offered are allowing complete control of the EC 2000 thru its serial port along with data acquisition.
DATA ACQUISITION Table 6: Ethernet IP/Serial Data Acquisition Item #1 Drive Speed in % 0 to 10000 Item #2 Drive Speed In RPM 0 to Max RPM Item #3 Reference 0 to 10000 Item #4 Set Point 0 to 10000 Item #5 Motor Amps (XFMR)
SECTION 10 – INDEX Item: Page(s) Acceleration/Deceleration 2, 7, 24, 29 Adjustable Braking 7, 10, 20, 22, 29 Analog Inputs 10, 17 Analog Outputs 10, 18, 31 Auto Reference 9, 10, 11, 17, 22, 31, 29, 34, 35, 41, 43 Auto Restart 9, 39 Brake Amps...
Page 45
Select Meter Set Point 9, 10, 11, 22, 30, 31, 32, 34-36, 40-43 Set Point Mode 10, 11, 31, 32 Setup 16-39 Source Select 34-35, 43 Specifications Speed Control 7, 9, 11, 20, 23, 25, 26 Speed Feedback 7, 9, 10, 20, 23, 25, 26, 28, 40, 41 Speed Feedback Scaling 23-26, 40 Speed Range...
Page 46
International, Inc. claims proprietary rights in the information disclosed hereon. This document is issue in confidence and is not to be reproduced or used to manufacture anything shown hereon without the written permission of Drive Source International, Inc. Drive Source International, Inc. Sturtevant, Wisconsin, USA 53177 Telephone: 262-554-7977 Fax: 262-554-7041 Toll Free: 800-548-2169 www.dynamatic.com sales@dynamatic.com...
Need help?
Do you have a question about the EC 2000 and is the answer not in the manual?
Questions and answers