6. SETTING FROM GX DEVELOPER

The intelligent function module switches are used to make the mode
setting, default operation setting, battery error detection setting, and
response monitoring time setting.
Switch number
Switch 1
Switch 2
Switch 3 (Lower byte)
Switch 4 to 5
(1) Mode setting (Switch 1)
Select the MES interface module operation mode.
Setting
number
0000h
0001h
0002h
(2) Default operation setting/battery error detection setting (Switch 2)
Select the default operation setting/battery error detection setting
for the MES interface module.
b15
to
Specify "0".*
Battery error detection setting
0: Detects battery errors.
1: Does not detect battery errors.
* When other than 0 is specified in this area, "Switch
setting error" (0180h) occurs at hardware test.
Mode setting
Default operation setting/battery error detection
setting
Response monitoring time setting
For system use (Do not set.)
Item
Online
Normal operation mode
Tests the ROM/RAM/intelligent function
Hardware test
module switch settings.
Self-loopback
Executes the 10BASE-T/100BASE-TX
test
interface self-diagnostics test.
b3
b2
7
Description
Description
b1
b0
Switch 2
Default operation setting [Account setting]
0: Operates according to [Account setting].
1: Operates according to the default.
User name
Password
Default operation setting [Network settings]
0: Operates according to [Network settings].
1: Operates according to the default.
IP ADDRESS :192.168.3.3
Subnet mask :255.255.255.0
:QJ71MES96