Table 39. Specifications for power cords used with the TS4500 tape library xx5 frame models (continued)
Length and type of power cord
Dual 4.3 m (14 ft.) 250 V ac, 15A, single phase
power cord, watertight 15A plugs. This power
cord is for US and Canada.
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10
A power cord with IEC 60320 C14 connector.
This power cord can be used worldwide to
connect to spare outlets on FC 1950 PDUs. It
can be used in an adjacent library frame or to a
customer-provided PDU that is mounted
external to the library frames.
Dual 4.3 m (14 ft.) power cords with NEMA
L6–30P non-watertight 30A plug, 200–240 V ac,
30 Amps. This power cord is for US, Canada,
Latin America, and Japan.
Dual 4.3 m (14 ft.) power cords with watertight
Russellstoll 3750DP 30A plug, 200–240 V ac, 30
Amps. This power cord is used in US, Chicago,
Canada, Latin America, and Japan.
Dual 4.3 m (14 ft.) power cords with IEC-309
p+n+g 32A plug, 200–240 V ac single phase, 32
Amps. This power cord is used in Europe, the
Middle East, and Africa.
Dual 4.3 m (14 ft.) power cords with PDL
56P332 32A plug, 200–240 V ac single phase, 32
Amps. This power cord is used in Australia and
New Zealand.
Dual 4.3 m (14 ft.) non-watertight power cords
with 30A plug type Shin Ju SJ-3302, 200–240 V
ac, 30 Amps. This power cord is used in North
and South Korea.
Dual 4.3 m (14 ft.) power cords, unterminated
(without a power plug), 200–240 V ac single
phase, 30 Amps maximum, with IRAM and
BSMI agency certifications. Wire size 4 mm
This is the recommended cord for Argentina,
Taiwan, Europe, the Middle East, and Africa if
an unterminated power cord is preferred.
Dual 4.3 m (14 ft.) power cords, unterminated
(without a power plug), 200–240 V ac single
phase, 30 Amps maximum, with CCC
certification. This is the recommended power
cord for China.
Note: Each feature code ships two power cords so that dual power is supported.
Power Receptacles
Part number
and feature
code
1
23R9972 / 9985
46X7337 / 9989
39M5416 / 9954
(Used with FC
1951 only)
39M5418 / 9955
(Used with FC
1951 only)
39M5414 / 9956
(Used with FC
1951 only)
39M5419 / 9957
(Used with FC
1951 only)
39M5420 / 9958
(Used with FC
1951 only)
23R7324 / 9959
2
.
(Used with FC
1951 only)
23R9543 / 9966
(Used with FC
1951 only)
Type of service receptacle
Russellstoll 3743U2 or 9R23U2W receptacles, or
Russellstoll 3913U2 or 9C23U2 connectors
Uses receptacle #9
IEC 60320 C13
Uses receptacle #13
NEMA L6–30R
Uses receptacle #10
Russellstoll 3753 or 9R33UOW receptacle, or a
Russellstoll 3933 or 9C33UO connector
Uses receptacle #11
IEC-309 p+n+g
Uses receptacle #2
1–gang, 3–pin 32A socket, PDL 56SO332 or
equivalent
Uses receptacle #12
200–250 V ac single phase
Uses receptacle #3
Not specified (no plug supplied)
Not specified (no plug supplied)