4. Arc Sensors

4.6 Sensor Connection

4.6.1 Arc Light Point Sensor EARF-01 Connection
1.
Open the sensor side covers and then detach the plug-
gable connectors from the sensor PCB and prepare the
twisted shielded pair cable connecting (see Figure 13).
Figure 13. EAFR-01 Sensor Connection Step 1.
2.
Before connecting the cable to connector, make sure
that the connecting order is correct (+, signal, shield).
The appropriate pins information is shown on the blue
bottom part of the sensor. Plug the wires into connec-
tor and fasten them by using a screw driver (see Figure
14).
Figure 14. EAFR-01 Sensor Connection Step 2.
3.
Connect the other end of the cable to a sensor channel
on the EAFR-101 or EAFR-110P relay (see Figure 15).
14
EAFR-110 Current and Arc Light Sensor Relay User Manual MN026007EN February 2016 www.eaton.com
Figure 15. EAFR-01 Sensor Connection Step 3.
4.
Check the front panel of the relay. Only the POWER
LED turns on at this moment (see Figure 16).
Figure 16. EAFR-01 Sensor Connection Step 4.
POWER LED
5.
Attach the connector back to the sensor PCB (see
Figure 17).
Figure 17. EAFR-01 Sensor Connection Step 5.