Table 5. 100 Ω Compatible Cables.
Manufacturer
Part No.
Belden
3074F
Belden
9841
Belden
89841
Figure 9. Cables Connected to the EAFR-01 with the
Covers Closed.
4.1.2 EAFR-01 Point Sensor Technical Data
Table 6. EAFR-01 Point Sensors Technical Data.
Light Intensity Threshold
Detection Radius
Mechanical Protection
Sensor Wiring Arrangement
Sensor Cable Specification
Maximum Sensor Cable Length per
Sensor Channel
Operating Temperature

4.2 Sensor Type Dependencies

Different sensor types can be utilized in different arc flash
protection relays of the EAFR series. Table 7 describes the
dependencies.
Table 7. Arc Sensor Dependencies.
EAFR-01
EAFR-06
EAFR-101
Yes
No
EAFR-102
No
Yes
EAFR-110P
Yes
No
EAFR-110F
No
Yes
Atten. dB/100 at 1 Mhz
Data AWG
0.34
18
0.60
24
0.60
24
8,000 Lux/25,000 Lux/50,000 Lux
180 Degrees
IP 64
Two Wires and Shield
Shielded Twisted Pair 0.75 mm2
(0.03 in.2)
200 m (656 ft)
-20 to 85°C (-4 to 185°F)
EAFR-07
EAFR-08
No
No
Yes
Yes
No
No
Yes
Yes
EAFR-101 Arc Point Sensor Relay User Manual MN026004EN February 2016 www.eaton.com
Cable Diameter mm (in.)
Temperature Rating °C (°F)
11.68 (0.46)
-40/+75 (-40/+167)
5.89 (0.23)
-30/+80 (-22/+176)
5.13 (0.20)
-70/+200 (-94/+392)

4.3 Sensor Connection

4.3.1 Arc Light Point Sensor EAFR-01 Connection
1.
Open the sensor side-covers, then detach the plug-
gable connectors from the sensor PCB, and prepare the
twisted shielded pair cable connecting (see Figure 10).
Figure 10. EAFR-01 Sensor Connection.
2.
Before connecting the cable to the connector, make
sure that the connecting order is correct (+, signal, and
shield). The appropriate pin information is shown on
the blue bottom part of the sensor. Plug the wires into
the connectors and fasten them by using a screw driver
(see Figure 11).
Figure 11. Location of the PIN Information and Securing
the Cable.
3.
Connect the other end of the cable to a sensor channel
on the EAFR-101 or EAFR-110P relay (see Figure 12).
4. Arc Sensors
Voltage Rating
600 V
300 V
300 V
9