3. Operation and Configuration

3.6 Dipswitch Settings

The EAFR-110 functionality, such as tripping logic, is config-
ured using the dipswitch settings. The relay contains two
switch groups SW1 and SW2 (see Figure 5). The dipswitch-
es are located at the back of the relay for easy access.
Figure 5. EAFR-110 Dipswitches SW1 and SW2.
S1 Sensor Channel 1:
S2 Sensor Channel 2:
S3 Sensor Channel 3:
Arc Configuration:
Type A
Configuration Select:
T1/T2:
HSO:
S1:
TBD on
S5:
Trip Relay:
CBFP Time:
100 ms
Phase Sensor:
Ground Sensor:
Table 2. EAFR-110 Dipswitch SW1 Setting.
Dipswitch
8
S1: Light / Light + Current
7
S2: Light / Light + Current
6
SX: Light / Light + Current.
5
a/b
4
Configuration select
3
Configuration select
2
Configuration select
1
Configuration select
8
EAFR-110 Current and Arc Light Sensor Relay User Manual MN026007EN February 2016 www.eaton.com
8
Light and Current
Light
Light and Current
7
Light
Light and Current
Light
6
Type B
5
4
3
2
1
SW1
Latch
Non Latch
8
Non Latch
Latch
7
TBD off
6
5
CBFP
Fast
4
150 ms
3
1 A
5 A
2
1 A
5 A
1
SW2
Function Selection
Sensor channel 1 trip criteria.
Sensor channel 2 trip criteria.
Sensor channels 3 - 5 trip criteria (channel 3
in EAFR-110F)
Selection of standard arc configuration type. Standard arc configurations
Selection of standard arc configuration.
Selection of standard arc configuration.
Selection of standard arc configuration.
Selection of standard arc configuration.
Different trip configurations can be easily programmed by
selecting the appropriate dipswitch settings. The most
convenient way to set the EAFR-110 single relay or more
complex arc protection system is to use the Standard Arc
Configurations (SACs). For different SAC applications, see
the "Standard Arc Configurations" manual (MN026009EN).
Tripping may be selected based on arc light only or current
thresholds. Other tripping criteria, such as under-voltage or
similar, may be applied instead of over-current as well using
binary inputs. The circuit breaker failure protection (CBFP)
configuration may also be enabled using the dipswitches.
See Table 2: EAFR-110 Dipswitch SW1 Setting and Table 3:
EAFR-110 Dipswitch SW2 Setting for details of settings.
ON (Left Position)
OFF (Right Position)
Trip on light only.
Trip on light and over-current. Both signals are
required simultaneously to trip.
Trip on light only.
Trip on light and over-current. Both signals are
required simultaneously to trip.
Trip on light only.
Trip on light and over-current. Both signals are
required simultaneously to trip.
Standard arc configurations type b.
type a.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.
Refer to MN026009EN.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eafr-06Eafr-110fEafr-102Eafr-01Eafr-08Eafr-07

Table of Contents