Troubleshooting Guide - Eaton EAFR-110 User Manual

Current and arc light sensor relay
Hide thumbs Also See for EAFR-110:
Table of Contents

Advertisement

3. Operation and Configuration
Table 1. LED Operation Quick Guide.
LED
Off
POWER
Auxiliary supply
Blue
disconnected.
ERROR
System healthy. System failure.
Red
T1
Normal status.
Red
T2
Normal status.
Red
T3
Normal status.
Red
T4
Normal status.
Red
S1
Normal status.
Amber
A S2
Normal status.
Amber
S3
Normal status.
Amber
S4
Normal status.
Amber
(N/A in EAFR-110F)
S5
Normal status.
Amber
(N/A in EAFR-110F)
BI1
Normal status.
Amber
BI2
Normal status.
Amber
BO1
Normal status.
Amber
IL1
Normal status,
Amber
actual current
below set point.
IL2
Normal status,
Amber
actual current
below set point.
IL3
Normal status,
Amber
actual current
below set point.
Ig
Normal status,
Amber
actual current
below set point.
HSO1
Normal status.
Red
HSO2
Normal status.
Red
6
EAFR-110 Current and Arc Light Sensor Relay User Manual MN026007EN February 2016 www.eaton.com
Steady On
Blinking
Auxiliary power connected. N/A
Configuration mismatch. Protection
partly operational.
Trip relay T1 activated.
N/A
Trip relay T2 activated.
N/A
Trip relay T3 activated.
N/A
Trip relay T4 activated.
N/A
Sensor channel 1 activated
Sensor channel 1 discontinuity or
by light information.
system setup not performed. Also acti-
vated by pressure information.
Sensor channel 2 activated
Sensor channel discontinuity or system
by light information.
setup not performed. Also activated by
pressure information.
Sensor channel 3 activated
Sensor channel 3 discontinuity or
by light information.
system setup not performed. Also acti-
vated by pressure information.
Sensor channel 4 activated
Sensor channel 4 discontinuity or
by light information (N/A in
system setup not performed. Also acti-
EAFR-110F).
vated by pressure information.
Sensor channel 5 activated.
Fiber sensor discontinuity or system
N/A in EAFR-110F
setup not performed.
Binary input 1 activated.
Binary input 1 loose connection.
Binary input 2 activated.
Binary input 2 loose connection.
Binary output activated.
N/A
IL1 current above the set
Open CT connection in channel IL1.
point.
IL2 current above set point. Open CT connection in channel IL2.
IL3 current above set point. Open CT connection in channel IL3.
Ground (earth fault) current
N/A
above set point.
HSO 1 activated.
N/A
HSO 2 activated.
N/A
Action if Abnormal
Check the power source.
Verify system condition. See Sections 11:
Troubleshooting Guide and 5: System Self-
supervision.
Check the reason for trip. Clear the fault and reset
indications by pushing SET button
Check the reason for trip. Clear the fault and reset
indications by pushing SET button
Check the reason for trip. Clear the fault and reset
indications by pushing SET button
Check the reason for trip. Clear the fault and reset
indications by pushing SET button
Check why the sensor activated, check the sensor
continuity, or perform a system setup (see Section
3.3.1: Auto Configuration (System Setup).
Check why the sensor activated, check the sensor
continuity, or perform a system setup (see Section
3.3.1: Auto Configuration (System Setup).
Check why the sensor activated, check the sensor
continuity, or perform system setup (see Section
3.3.1: Auto Configuration (System Setup).
Check why the sensor activated, check the sensor
continuity, or perform system setup (see Section
3.3.1: Auto Configuration (System Setup).
Check why the sensor activated, check the sensor
continuity, or perform system setup (see Section
3.3.1: Auto Configuration (System Setup)
Check the binary input wiring.
Check the binary input wiring.
Check the current set point levels or check the CT
wiring.
Check the current set point levels or check the CT
wiring.
Check the current set point levels or check the CT
wiring.
Check the earth current set point level.
Check the reason for activation. Clear the fault and
reset indications by pushing SET button.
Check the reason for activation. Clear the fault and
reset indications by pushing SET button.