Carrying Out Testing In Light And Current Mode; Testing The Cbfp Function; Testing The Arc Flash Protection Unit Operation Time - Eaton EAFR-110 User Manual

Current and arc light sensor relay
Hide thumbs Also See for EAFR-110:
Table of Contents

Advertisement

9. Testing

9.2 Carrying Out Testing in Light and Current Mode

1.
Check that the dipswitch setting positions are in accor-
dance with your application.
2.
Activate the camera flash within 20 cm (8 in.) of the
EAFR-01 sensor relay and simultaneously activate the
binary input BI1 used for over-current condition.
3.
Verify that the sensor channel indication LED status is
changed to ON.
4.
Verify that the binary input indication LED status is
changed to ON.
5.
Verify the relay output(s) activation(s) by checking the
circuit breaker status or by monitoring trip contact sta-
tus.
N
otee:
A best practice is to operate circuit breaker at test-
ing. The circuit breaker should open or contacts
operate.
6.
Verify that the corresponding relay output(s) LED(s) indi-
cation status is changed to ON.
7 .
If the binary output (BO1) signal is utilized, verify the
BO1 signal activation by the status change of the rele-
vant input where the binary output signal is connected,
or by measuring the signal output voltage.
8.
If a binary output or high speed output (HSO) signal
is utilized, verify that BO1 LED or the relevant HSO
LED is illuminated. Note that the BO1 signal is a non-
latched type.
9.
If the other binary input (BI2) is in use, verify correct
operation by activating the input.
10. Activate the camera flash within 20 cm (8 in.) from the
EAFR-01 sensor relay and do not activate the binary
input used for over-current condition.
11. Verify that no trip has occurred and only the sensor acti-
vation indication LED is ON.
12. Verify that the BO1 signal is activated (if in use and con-
figured to send light information).
13. Press the SET push-button to reset all indications and
latches.
14. If the binary input BI2 is utilized for master trip to acti-
vate the BI2, verify that a trip has occurred by repeating
Steps 4 and 5.
15. Press the SET push-button to reset all indications and
latches.
16. Repeat the testing procedure for all sensors.
24
EAFR-110 Current and Arc Light Sensor Relay User Manual MN026007EN February 2016 www.eaton.com

9.3 Testing the CBFP Function

The circuit breaker failure function is tested by leaving light
signal and second trip criteria signal (e.g. over-current), if
applicable, active for above the set CBFP time of either 100
or 150 ms. The trip relay T2 and binary output BO1 should
be active after the set time delay.
9.4 Testing the Arc Flash Protection Unit Operation
Time
The EAFR-110 operation time test is not required at com-
missioning as it is performed by the manufacturer as a type
test and routine production test. Refer to the routine test
reports sent with EAFR-110 relay and consult your nearest
Eaton representative for type test reports.
However, if it is deemed necessary, a site timing test may
be conducted using the instructions that follow.
1.
Use a calibrated relay test set.
2.
Connect an output from the relay test set to the cam-
era flash or equivalent input for initializing the flash and
configure a relay test set timer to be started simultane-
ously with flash.
3.
Connect EAFR-110 trip output T1,T2, T3, or T4 or high
speed outputs HSO1 or HSO2 to relay test set input
and configure the input to stop the timer.
4.
Place camera flash to maximum 20 cm (8 in.) distance
of the EAFR-01 or EAFR-07 sensor.
5.
Initiate the flash and timer using the relay test set out-
put.
6.
Read the measured time between simulated arc and
trip contact operation.
7 .
Subtract the digital input delay of the relay test set
from the final measured time if applicable. For specific
test instructions consult the manufacturer of the relay
test set.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eafr-06Eafr-110fEafr-102Eafr-01Eafr-08Eafr-07

Table of Contents