Summary of Contents for Eaton EAFR-101S
Page 1
MN026005EN EAFR-101S Arc Point Sensor Relay User Manual...
Page 2
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other- wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or...
– Millisecond The EAFR-101S can be used as a stand-alone relay or as part of a more complex arc protection system through the – Medium voltage binary bus.
Page 6
2. General Figure 1. The EAFR-101S Arc Protection IO Relay. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
T2,T3 24Vdc Light / Light and Current S1: Light / Light and Current Self supervision Latch / Non Latch Control and power supply 100 / 150 ms Configuration Select EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
When re-powering the relay after power sup- ply loss, the actual LED status can be visualized from the front of the relay. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Refer to Sections 3.5.1 and 6. Configuration selection. Refer to Sections 3.5.1 and 6. Refer to Sections 3.5.1 and 6. Configuration selection. Refer to Sections 3.5.10 and 6. Refer to Sections 3.5.1 and 6. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 11
The detailed instruction is described in EAFR Standard Arc Configurations booklet. Table 3. General Trip Logic for the EAFR-101S Standard Arc Configuration 1. Tripping Signals Fault Location EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 12
BI6 are used for sending light information from a different location of the busbar. BO1, BO2, and BO3 send arc fault information to incoming feeder units and the intermediate units. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 13
BI6 are used for sending light information from the different location of the busbars. BO1, BO2, and BO3 send arc fault information to the incoming feeder units and intermediate units. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 14
BI3 and BI4 receive over-current information from the two Tripping Signals Fault main busbar sections respectively. BO1 and BO3 represent Location the arc fault detected at both main busbar sections. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 15
EAFR-110P relays. BI3 and BI4 receive over- Location current information from both incoming EAFR-110P relays. BO1 and BO3 send detected arc fault information from the busbar and section CB to both incoming EAFR-110P relays. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 16
BI3 receives over-current information from the EAFR-110P of incoming feeder. BI4, BI5, and BI6 are used for sending light information from a different location of the busbar. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 17
BI3 receives over-current information from the EAFR-110P of the incoming feeder. BO1 sends light information to the EAFR-110P of the incoming feeder when there is any arc fault detected by the EAFR-101S. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 18
EAFR-110P of the incoming feeder. BO1 sends light infor- mation to the EAFR-110P of incoming feeder when there is any arc fault detected by EAFR-101S. The CBFP module is applied in this configuration. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Page 19
BI6 are used for sending light information from different locations of the busbars. BO1, BO2, and BO3 send arc fault information to the incoming feeder units and intermediate units. The CBFP feature is applied in this configuration. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Non-volatile memory does not require a power supply to tion to the incoming feeder units and intermediate units. maintain information and will retain settings and indications The CBFP feature is applied into this configuration. permanently without power. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
6. Application Examples 4.1.2 EAFR-01 Point Sensor Technical Data Table 9. EAFR-01 Point Sensors Technical Data. The EAFR-101S may be applied to a variety of power switch- gear and control gear layouts and technologies. Some typi- Light Intensity Threshold 8,000 Lux/25,000 Lux/50,000 Lux cal applications are described in this section.
The breaker failure function is activated if the EAFR-101S detects the presence of light after a set operat- ing time. When the EAFR-101S is set to operate on light and current, both parameters must persist to activate CBFP .
The EAFR-101S has four arc point sensor channels. A maxi- mum of three arc point sensors (type EAFR-01) may be con- nected to each channel. For details on sensors refer to Section 4: Arc Sensors. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
Figure 18. Wiring Diagram of the EAFR-101S Relay. Station battery EAFR-101S Light / Light and Current S1: Light / Light and Current Latch / Non Latch 100 / 150 ms Configuration Select EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
19 in. (482.6 mm) rack (height of 4U and 1/8 of a unit wide). Figure 19. EAFR-101S Dimensions in Millimeters (In.) (Side View). 175 (6.89) 160 (6.30) 10 (0.39) 17 (0.67) 157 (6.18) 10 (0.39) EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
The BO1 signal is a non-latched type. If a binary output signal is utilized, verify that the BO1 LED is illuminated. Press the SET push-button to reset all indications and latches. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
The EAFR-101 operation time test is not required at com- missioning as it is performed by Eaton as a type test and Activate the camera flash within 20 cm (8 in.) of the routine production test. Refer to the routine test reports...
* = Total trip time using arc light or phase/residual over-current from Trip relay(s) does not Dipswitch settings Section 3.5 of this EAFR-110 and arc light. operate even if sensor is manual activated. EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...
12.10 Environmental Conditions Specified Ambient Service Temp. Range -35 to 70°C (-31 to 158°F) Transport and Storage Temp. Range -35 to 70°C (-31 to 158°F) Relative Humidity Up to 97% EAFR-101S Arc Point Sensor Relay User Manual MN026005EN February 2016 www.eaton.com...