3.10 Analog Output Configuration

Overview.
Fitted analog outputs – assignable to retransmit any process variable
Selectable analog output range – allows maximum resolution on range of interest
Adjustable output range – for non-standard and reversed outputs
The example below shows analog output 1 programmed to retransmit part of process variable 1's engineering range (250 to 750°C)
as a 4.0 to 20.0 mA current output.
Select Analog
Select Output
Output
Source
Position 1
PV1
PV2
PV3
PV4
Positiont 6
IM/C1300 Rev. J
1000°C (Engineering Range High)
750°C (Analog Output Range High)
Range to be
transmitted
250°C (Analog Output Range Low)
0°C (Engineering Range Low)
Analog Output Configuration
Press the
key to open the Main Menu.
Highlight Analog Output.
Select Analog Output
Select the analog output to be configured.
Analog Output Source
Select the source for the analog output.
Refer to Appendix A on page 77 for a description of sources.
Continued on next page.
Setting Output Ranges
20.0mA (Output Range High)
4.0mA (Output Range Low)