6 Disconnect the connectors.
Precaution
When disconnecting the motor connectors, make sure
that the power supply is turned off. Even when the fan
motor is stopped, disconnecting the live-line connectors
will cause a motor malfunction.
For LGH-250RVXT-E
7 Unscrew the screws (four PTT screws 5×10, indicated by ) for the fan base of the air supply fan (outside
unit).
Notes:
• The fan bases of the inside units are not provided with these screws.
• The figure and picture show the air supply fan assembly. Remove the screws for the air exhaust fan (out-
side unit) in the same way.
For LGH-250RVXT-E
8 Slide the fan base toward back side.
Note: The inside units cannot be moved.
─ 37 ─
Fan base
Fan base