Mitsubishi Lossnay LGH-150RVXT-E Handbook page 32

Table of Contents

Advertisement

Error
LED1
LED2
Code
(green)
(red)
6801
9
PZ-43SMF-E
blinks
communica-
tion error
6831
9
PZ-61DR-E
blinks
communica-
tion error (no
reception)
6832
9
PZ-61DR-E
blinks
communica-
tion error
(synchroniza-
tion recovery
error)
Symptom
Multiple PZ-43SMF-E transmission
cables are wired using multicore
cables.
The power supply cable is too close
to the PZ-43SMF-E transmission
cable.
Faulty connection of the PZ-
43SMF-E transmission cable
The wiring length of the PZ-43SMF-E
transmission cable is longer than
specified (200 m or more).
The Lossnay is used in the same
group as LGH-RX
PZ-43SMF-E is connected to the
terminals (TB5 [A] [B]).
Remote controller (PZ-43SMF-E)
failure
Faulty connection of the PZ-61DR-E
transmission cable
The Lossnay is used in the same
group as LGH-RX
PZ-61DR-E is connected to the ter-
minals (TB5 [A] [B]).
Remote controller (PZ-61DR-E)
failure
Faulty connection of the PZ-61DR-E
transmission cable
The Lossnay is used in the same
group as LGH-RX
Remote controller (PZ-61DR-E)
failure
Cause
-E type Lossnay.
5
-E type Lossnay.
5
-E type Lossnay.
5
─ 32 ─
Corrective action
Using the applicable cable, wire
the transmission cable away from
one another.
Wire the power supply cable at
least 5 cm away from the trans-
mission cable.
Check the transmission cable con-
nections.
Check the wiring length of the
transmission cable.
The LGH-RVXT-E type Lossnay
cannot be used in the same group
as LGH-RX
-E type Lossnay.
5
Connect PZ-43SMF-E to the
terminals (TM4 1 2). (See the
Lossnay technical manual.)
Replace the remote controller (PZ-
43SMF-E).
Check the items described in (1)
2.
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
circuit board or PZ-61DR-E remote
controller.
The LGH-RVXT-E type Lossnay
cannot be used in the same group
as LGH-RX
-E type Lossnay.
5
Connect PZ-61DR-E to the ter-
minals (TM4 12). (See the
Lossnay technical manual.)
Replace the remote controller (PZ-
61DR-E).
Check the items described in (1)
2.
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
circuit board or PZ-61DR-E remote
controller.
The LGH-RVXT-E type Lossnay
cannot be used in the same group
as LGH-RX
-E type Lossnay.
5
Replace the remote controller (PZ-
61DR-E).

Hide quick links: