Mitsubishi Electric MELSEC-Q series Programming Manual page 45

Qna programming manual (pid control instructions)
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

Setting
Data
Data Item
data
No.
Data for
9
MV change
each loop
rate limit (
MVL)
10
PV change
rate limit (
PVL)
11
Derivative
gain (K
)
D
Description
Incomplete derivative
With PID limits
Setting
Range
Sets the limit for variation
0 to 2000
between the previous MV
and present MV.
When the MV variation is
greater than the limit
value, 1 is set for bit 1
(b1) of the alarm device.
Does not limit the MV
variation. (If the MV
variation is greater than
the limit value, it is used
unchanged as the MV
variation to calculate the
MV.)
Sets the limit for variation
0 to 2000
between the previous PV
and present PV.
When the PV variation is
greater than the limit
value, 1 is set for bit 0
(b0) of the alarm device.
Does not limit the PV
variation. (If the PV
variation is greater than
the limit value, it is used
unchanged as the PV
variation to perform the
PID operation.)
Sets a time period
0.00 to
(operation delay) for
300.00
derivative operation.
(Ideal value
As the value is greater,
is 8.00)
the time period
Infinite()
decreases and operation
(If the setting
becomes closer to
for K
D
complete derivative.
exceeds
300.00)
Without PID limits
User
Setting
User
Specification
Range
Specification
Range
Range
0 to 2000
-32768 to
-32768 to
32767
32767
0 to 2000
-32768 to
-32768 to
32767
32767
0 to 32767
0.00 to 300.00
0 to 32767
(unit: 0.01)
(Ideal value is
(unit: 0.01)
8.00)
Infinite()
(If the setting
for K
D
exceeds
300.00)
5 PID CONTROL PROCEDURE
Processing
when Set Data
is Outside the
Allowable
Setting Range
In the case of
"with PID limits",
PID operation is
performed after
conversion into
the following
value.
• When the MVL
value is less
than 0, it is
converted into
0.
• When the MVL
value is greater
than 2000, it is
converted into
2000.
In the case of
"with PID limits",
PID operation is
performed after
conversion into
the following
value.
• When the PVL
value is less
than 0, it is
converted into
0.
• When the PVL
value is greater
than 2000, it is
converted into
2000.
An error occurs
and PID operation
for the
corresponding
loop is not
executed.
43
5.1 PID Control Data